Coils / Thermistors

5. Coils / Thermistors
Warning
Step
1. Remove the electronic
expansion valve coils.
1
Cut the 3 clamps.
2
Pull out the electronic
expansion valve coils.
2. Remove the thermistors.
1
Cut the clamps and pull
out the gas pipe
thermistors.
16
Be sure to wait for 10 minutes or more after turning off all power supplies before
disassembling work.
Procedure
Electronic
expansion
valve coil
The number of electronic
expansion valve coils and
thermistors varies depending
on the model.
Clamp
(R17991)
Clamp
(R17992)
Be careful not to lose the
clips for the thermistors.
Gas pipe thermistor
Clip
Si121293EC
Points
(R18102)
Removal Procedure