Download Print this page

Dimensions; Installation Instructions - Panduit VeriSafe VS2-NET Installation Manual

Network module
Hide thumbs Also See for VeriSafe VS2-NET:

Advertisement

Dimensions

Dimensions

Installation Instructions

Special Conditions
of Use
WARNING:
Always de-energize power before accessing an electrical enclosure
Always follow safety and lockout/tagout procedures when working on or near electrical systems and equipment
Do not use this product outside of the specified performance and environmental limits
Always comply with local installation codes and standards
The data from the network module does not carry a functional safety rating . It should be used for monitoring only . If integrating
with a safety-rated system, use the SIL 3 outputs on the AVT isolation module instead of the network module outputs .
STEP 1: INSTALL NETWORK MODULE INTO ENCLOSURE
Mount network module flat in enclosure (see *NOTE in dimensional diagram above), or
Snap the network module onto the DIN rail, or
Mount the network module to the 2 .0 AVT isolation module . See image to the right .
STEP 2: CONNECT POWER TO NETWORK MODULE (DC POWER SUPPY, OR POWER OVER ETHERNET)
Connect power supply to DC Input, or connect PoE network cable to PoE connection
STEP 3: CONNECT THE DATA/POWER OUTPUT FROM NETWORK MODULE TO 2.0 AVT ISOLATION MODULE
Connect wires into pluggable screw terminal connectors on network module and the 2 .0 AVT
isolation module . The connector ports are labeled "AVT" .
STEP 4: CONNECT NETWORK CONNECTION TO RJ-45 PORT
if using the DC Input connector for power, and not using PoE, connect RJ-45 network cable,
if using PoE, connect the PoE network cable to RJ-45 port
STEP 5: BEFORE POWER-UP, READ DOCUMENT B21110 (2.0 AVT INSTRUCTION MANUAL) AND DOCUMENT B21176
(NETWORK MODULE USER GUIDE) FOR USER AND WEB-INTERFACE INSTRUCTIONS. POWER UP THE SYSTEM.
10/16/2022
135 x 112 x 28 mm (5 .3 x 4 .4 x 1 .1 inches), when network connetion is installed
Hazardous Locations
The equipment shall be installed in an enclosure that provides a degree of protection not less than
IP 54 in accordance with IEC 60079-0 .
Ambient Temperature Range: -25°C ≤ Tamb ≤ 60°C
The enclosure must only be accessible with use of a tool .
NOTE*:
For mounting the network module flat in an enclosure,
use the hole pattern locations identified by "A" in the
diagram . Use four #6 [M3 .5] pan head screws or
other compatible fasteners .
5
IF DESIRED, ATTACH NETWORK MODULE
TO THE 2 .0 AVT ISOLATION MODULE USING
SCREWS PROVIDED WITH THE NETWORK
MODULE