Download Print this page

System Overview; Power Inputs; Avt Connection; Voltage Presence Outputs - Panduit VeriSafe VS2-NET Installation Manual

Network module
Hide thumbs Also See for VeriSafe VS2-NET:

Advertisement

System Overview

Termination Resistor Switch
+
+
DC Intput

POWER INPUTS

The power supply must be surge protected, otherwise
external surge protection is required at the input to the supply .
IEC Class I regulated power supply
Min . Output: 12 VDC @ 100mA, 24 VDC @ 50mA
Connector / Wiring Requirements
Wire Range: AWG #24 - 14 SOL / STR (1 wire only)
Wire strip length: 9 .0mm (min) / 10 .0mm (max)

AVT CONNECTION

Provides power and communications to the AVT isolation module . The connection features a pluggable screw terminal connector .
Only install the network module in the same electrical enclosure as the VeriSafe 2 .0 AVT isolation module .
Recommended Wiring

VOLTAGE PRESENCE OUTPUTS

Reflects status of Voltage presence LEDs on the AVT indicator module . These outputs are updated every 2 seconds based on the state
reported from the AVT isolation module . These outputs are not an indication of absence of voltage .
3 Solid-state Relay
Normally open, relays close when red AVT indicators are
Output Contacts
illuminated (see AVT manual for red indicator voltage thresholds)
Wire Size
AWG #26-16 AWG (0 .13 - 1 .3mm
Isolation
5000 Vrms Input/Output
Voltage Rating
30V AC/DC
Current Rating
80 mA (max)
On-resistance
30 Ω
10/16/2022
1A 1B 2A 2B 3A 3B
AVT
+
AVT Connection
Voltage Presence
Contacts
DC Input
When using the network module with the 2 .0 AVT isolation module, the
network module "AVT Connection" supplies power from the network module
to the isolation module . Therefore DO NOT apply an external power source
to the 2 .0 AVT isolation module when used with the network module .
Network
1
Module
Isolation
2
Module
Output Specification
) Solid/Stranded (1 wire only)
2
Network
System Status
Connection
0
10/100 P
E
Power Status
Reset Button
(not shown)
10/100 PoE
IEEE 802 .3af Type 1 Class III PoE topology .
Connector Specifications
Connector / Wiring Requirements;
Wire Range: (1 wire): AWG #24 - 12 [2 .5mm2] SOL / STR
(2 wire): AWG #18 [1 .0mm2] SOL
Wire strip length: 7 .0mm (min) / 8 .0mm (max)
Screw Drive Size: M3x0 .5
Screw Torque Required: 5 .0 in-lb [0 .57 N-m] +/- 10%
3
The termination resistor
switch below the AVT
connection ports on the
network module and AVT
isolation module shall be
positioned to the right
(factory default) when
facing the port
Network Connection (PoE)
AWG #18 [1 .5mm2] STR
Output schematic
1A
1B
2A
2B
3A
3B
1006772, B21148_EN_rev1