Technical Specifications

WARNING
Do not use this product outside of the specified performance and environmental limits . Failure to comply with
:
these specifications could result in product failure, personal injury, or death.
Operating Temperature
Storage Temperature
Humidity
Pollution Degree
Altitude
Degree of Protection
Special Conditions
of Use
Network Module
(Hazardous Location Ratings)
DC Input
Power over EtherNet (PoE)
IEC / UL / CSA C22 .2 NO . 61010-1
IEC / UL / CSA C22 .2 NO . 61010-2-030
UL 508 & CSA-C22 .2 No . 14
FCC - CFR 47 Part 15 Subpart B
CAN ICES-001
EN 55011, CISPR 11,
AS/NZS CISPR 11
IEC 61326-1
EN 61326-1
IEC / EN 61000-3-2, -3-3, -6-2
CE
UKCA
RoHS
E489576
Absence of Voltage
Accessory
Ind. Cont. Eq.
1006772, B21148_EN_rev1

Environmental Ratings

-25°C to 60°C (-13°F to 140°F)
-45°C to 85°C (-49°F to 185°F)
5 to 90% non-condensing; Rated 80% at 40°C (104°F), decreasing linearly to 50% at 60°C (140°F)
3
Up to 5000 meters (16400 feet)
Open Type, IP20
Hazardous Locations
The equipment shall be installed in an enclosure that provides a degree of protection not less than
IP 54 in accordance with IEC 60079-0 .
Ambient Temperature Range: -25°C ≤ Tamb ≤ 60°C
The enclosure must only be accessible with use of a tool .
cULus: Class I, Division 2, Groups A, B, C, D
Class I Zone 2 AEx ec IIC T5 Gc; Ex ec IIC T5 Gc

Power Requirements

The power supply must be surge protected, otherwise external surge protection is
required at the input to the supply .
12-24 VDC (IEC Class I regulated power supply) Min . Output: 12 VDC @ 100 mA, 24 VDC @ 50 mA
Power Draw: 84 mA max @ 12 VDC; 42 mA max @ 24 VDC (Network Module + AVT)
PoE (10/100), 15 mA, IEEE 802 .at (-af) Type 1 Class III PoE topology

Standards and Certifications

Safety requirements for electrical equipment for measurement, control, and laboratory use
Industrial control equipment
Radio frequency devices
Industrial, scientific and medical (ISM) radio frequency generators
Radio frequency disturbance characteristics
EMC and immunity requirements
Electromagnetic compatibility (EMC)
Conformity Marking for European Economic Area
Conformity Marking for United Kingdom
Restriction of hazardous substances