24
IBM System Storage SAN Volume Controller: Installation Guide
Environment
Environment
Temperature
Operating in
10°C to 35°C
lower altitudes
(50°F to 95°F)
Operating in
10°C to 32°C
higher altitudes
(50°F to 88°F)
Powered off
10°C to 43°C
(50°F to 110°F)
Storing
1°C to 60°C
(34°F to 140°F)
Shipping
-20°C to 60°C
(-4°F to 140°F)
Preparing your SAN Volume Controller 2145-4F2 environment
The following four tables list the physical dimensions and weight of the SAN
Volume Controller 2145-4F2 node, as well as other environmental requirements that
you must consider before you install your SAN Volume Controller 2145-4F2.
Dimensions and weight
Height
Width
43 mm
440 mm
(1.69 in.)
(17.32 in.)
Additional space requirements
Location
Left and right sides
Back
AC input-voltage requirements
Power supply
assembly type
200 to 240 V
Relative
Altitude
humidity
0 to 914 m
8% to 80%
(0 to 2998 ft)
noncondensing
914 to 2133 m
8% to 80%
(2998 to
noncondensing
6988 ft)
8% to 80%
noncondensing
0 to 2133 m
5% to 80%
(0 to 6988 ft)
noncondensing
0 to 10668 m
5% to 100%
(0 to 34991 ft)
condensing,
but no
precipitation
Depth
686 mm
(27 in.)
Additional space
requirements
50 mm
(2 in.)
Minimum:
100 mm (4 in.)
Voltage
88 to 264 V ac
Maximum
wet bulb
temperature
23°C
(74°F)
23°C
(74°F)
27°C
(81°F)
29°C
(84°F)
29°C
(84°F)
Maximum weight
12.7 kg
(28 lb.)
Reason
Cooling air flow
Cable exit
Frequency
50 or 60 Hz