Flue and ventilation

Advertisement

Bosch Flue and Ventilation Quick Reference Guide 2022
Plume Management Kit termination clearances
The plume terminal outlet must follow the conditions outlined in
to the tables below for minimum distance from an opening. This is to prevent products of combustion from entering the building
via an opening and damage to any building fabric.
Figure 9
Reference
1
(Figure
9)
9
(Figure
4) &
(Figure
8)
G
(Figure
10)
F
(Figure
10)
Please note: When installing the Plume management kit, it is important to check that the Air inlet is at least 2m from ground level
if a terminal guard is not used.
If this cannot be achieved then the implementation of an Air inlet adaptor is required (7-738-113-147), the standard air intake will
be capped off with the supplied blanking plate, and the air adaptor then placed higher up the termination to achieve the 2m
minimum distance from ground level.
Figure 11
Whilst it is always our intention to fully assist, it is essential to recognise that all information given by the company in response to an enquiry of any nature is provided in good faith and based
upon the information provided with the enquiry. We recommend that advice should always be checked with your installer or contract partner. Consequently, the company cannot be held
responsible for any liability relating to the use or repetition of such information or part thereof. In addition, whilst making every reasonable effort to monitor the performance and quality of
our supply, installation and service network, we do not accept responsibility for the workmanship or operation of any third party company that the company may have promoted either in
conversation, e-mail, or other communication. Similarly, the views and opinions expressed in communication with individuals within the company may not reflect that of the business as a whole.
You can find this, and all issued technical bulletins on the Worcester website at: worcester-bosch.co.uk/tb or worcester-bosch.ie/tb
Worcester, Bosch Group, Cotswold Way, Warndon, Worcester WR4 9SW Technical Services: 0330 123 3366 | technical-advice@uk.bosch.com
Description
Terminal to Opening
Terminal below Opening
Terminal to Terminal
Terminal to Surface
Figure
9. When directing the plume discharge outlet please refer
Figure 10
Unit
50 kW
65 kW
mm
300
300
mm
300
300
mm
1200
1200
mm
600
600
85 kW
100 kW
125 kW
687
792
948
2500
2500
2500
2232
2512
2930
1278
1613
2113
145 kW
1107
2500
3355
2622
10