Page 2
BS5440-2:2009 (supply only to single boilers). With reference to any boiler below 70 kW Input (GC 7000 WP 50 kW & 65 kW condensing boilers only). Please note: Groups of boilers exceeding 70 kW net are covered by IGEM-UP-10 (Edition 4) and BS6644:2011.
Page 3
Similarly, the views and opinions expressed in communication with individuals within the company may not reflect that of the business as a whole. You can find this, and all issued technical bulletins on the Worcester website at: worcester-bosch.co.uk/tb or worcester-bosch.ie/tb...
Page 4
Similarly, the views and opinions expressed in communication with individuals within the company may not reflect that of the business as a whole. You can find this, and all issued technical bulletins on the Worcester website at: worcester-bosch.co.uk/tb or worcester-bosch.ie/tb...
Page 5
– with reference to IGEM-UP-10 (Edition 4) – 7.2 – Figure 2. Figure 3 Example: Based on 4 x GC 7000 WP 100kW boilers @ 96.5 kW Net heat input, placed within a boiler room that has a summer usage below 50% Low level ventilation: 4 x 96.5 kW = 386 kW x 4cm²...
Page 6
3.95 x (Net heat input kW) Example: Based on 4 x GC 7000 WP 100kW boilers @ 96.5 kW Net heat input, placed within a boiler room that has a summer usage below 50% Inlet ventilation = 2.6 m 3 h x 386 (Total net heat input kW) = 1003.6 m 3 h...
Similarly, the views and opinions expressed in communication with individuals within the company may not reflect that of the business as a whole. You can find this, and all issued technical bulletins on the Worcester website at: worcester-bosch.co.uk/tb or worcester-bosch.ie/tb...
Page 8
Flue terminal positions in accordance with IGEM-UP-10 (Edition 4) – minimum required distance. Please note: For the GC 7000 WP 50 kW & 65 kW boilers, the below figures are only used when multiple units are being cascaded together (refer to IGEM-UP-10), for single installations of the GC 7000 WP 50 kW & 65 kW boilers, please refer to Figure 4 of this document to follow the guidance BS5440-1:2008.
Page 9
70 kW the risk assessment in ‘appendix 9’ used for horizontal terminations complying with IGEM/UP/10 Edition 4, does not permit flue terminations within a light well. Therefore, this applies only to single GC 7000 WP 50 kW or 65 kW boilers.
Page 10
Similarly, the views and opinions expressed in communication with individuals within the company may not reflect that of the business as a whole. You can find this, and all issued technical bulletins on the Worcester website at: worcester-bosch.co.uk/tb or worcester-bosch.ie/tb...
Page 11
Similarly, the views and opinions expressed in communication with individuals within the company may not reflect that of the business as a whole. You can find this, and all issued technical bulletins on the Worcester website at: worcester-bosch.co.uk/tb or worcester-bosch.ie/tb...
Page 12
– page 46 (formula to calculate distance G = 19.32 x Net head input (kW) +647.59) 5U the distance for GC 7000 WP appliances can be found on page 12 of this document. Section 1 Type C (room sealed) appliances with net heat exceeding 70kW and not exceeding 333kW low level flue discharge risk assessment, (including net heat input for groups of appliances).
Page 13
Similarly, the views and opinions expressed in communication with individuals within the company may not reflect that of the business as a whole. You can find this, and all issued technical bulletins on the Worcester website at: worcester-bosch.co.uk/tb or worcester-bosch.ie/tb...
Page 14
Similarly, the views and opinions expressed in communication with individuals within the company may not reflect that of the business as a whole. You can find this, and all issued technical bulletins on the Worcester website at: worcester-bosch.co.uk/tb or worcester-bosch.ie/tb...
Page 15
Figure 16 Figure 17 Example (See Figure 17) 4x GC 7000 WP @ 386 kW Net heat input = 0.859U, Building Height = 9m Chimney height (H ) = Building Height (H ) + 0.6U = 9 + 0.6 x 0.859 (1) = 10m (Round up to the nearest meter) •...
Page 16
CO detection must result in a boiler shut off and prevent CO exposure. With our GC 7000 WP range, all Bosch Cascade base flue kits contain a CO detector for on-site wiring into our CC8313 controller or MC400 Cascade controller, where these controllers are not used due to controls from a BMS system it is still a requirement that the BMS has some form of CO detection thus activating a boiler shut off.