Flue and ventilation

Advertisement

Bosch Flue and Ventilation Quick Reference Guide 2022
Table below is direct reference to
IMAGE NO: DESCRIPTION
1
300mm adjacent to a boundary line
The dimension below eaves, balconies and car ports can be reduced to 25mm, as long as the flue terminal is extended to clear any overhang. Any external flue
2
joints MUST be sealed with suitable silicon sealant
1,500mm between a vertical flue terminal and a window or dormer window, 300mm between two flue terminals
3
at multiple heights, please see fig 7/8.
4
1,200mm between terminals facing each other
5
Vertical flue clearance, 300mm adjacent to a boundary line
600mm distance to a boundary line unless it causes a nuisance. BS5440: Part 1 recommends that care is taken when siting terminal in relation to boundary lines
6
600mm minimum clearance from a skylight to a vertical flue
7
Vertical flue clearance, 500mm to non-combustible building material, and 1,500mm clearance to combustible building material
8
300mm above, below, or either side of an opening door, air vent or opening window
9
600mm diagonally to an opening door, air vent or opening window
10
300mm to an internal or external corner
11
2,000mm below a Velux window, 600mm above or to either side of the Velux window
12
400mm from a pitched roof or in regions with heavy snow fall 500mm
13
500mm clearance to any vertical structure on a roof, 600mm to a room sealed flue or 1,500 to an open flue
14
200mm below eaves and 75mm below gutters, pipes, and drains
15
The dimension below eaves, balconies and car ports can be reduced by 25mm, making sure the flue terminal is extended to clear any overhang. Any external flue joints
16
MUST be sealed with suitable silicon sealant
Flue clearance must be at least 300mm from the ground. Terminal guards must be fitted if the flue is less than 2 metres from the ground. Terminal guards must be fitted if
17
the flue is less than 2 metres from the ground or if a person could come into contact with the flue terminal
600mm distance to a surface facing a terminal unless it will cause a nuisance. BS 5440: Part 1 recommends that care is taken when siting terminals in relation to surfaces
18
facing a terminal
Flue terminal positions in accordance with IGEM-UP-10 (Edition 4) – minimum required distance.
Please note: For the GC 7000 WP 50 kW & 65 kW boilers, the below figures are only used when multiple units are being
cascaded together (refer to IGEM-UP-10), for single installations of the GC 7000 WP 50 kW & 65 kW boilers, please refer
to Figure 4 of this document to follow the guidance BS5440-1:2008.
Figure 5:
Reference
IGEM Calculation used
(See figure 4 & 6)
N/A
3
Distance G – (IGEM-UP-10, Fig. 12)
4
(Distance G = 19.32 x (net heat input kW) + 647.59)
7
N/A
Distance Y – (IGEM-UP-10, Fig. 7)
9
(Distance Y = 7.232 x (net heat input kW) + 93.708)
Distance F –
(IGEM-UP-10, Fig. 12)
18
(Distance F = 23.126 x (net heat input kW) - 618.84)
Whilst it is always our intention to fully assist, it is essential to recognise that all information given by the company in response to an enquiry of any nature is provided in good faith and based
upon the information provided with the enquiry. We recommend that advice should always be checked with your installer or contract partner. Consequently, the company cannot be held
responsible for any liability relating to the use or repetition of such information or part thereof. In addition, whilst making every reasonable effort to monitor the performance and quality of
our supply, installation and service network, we do not accept responsibility for the workmanship or operation of any third party company that the company may have promoted either in
conversation, e-mail, or other communication. Similarly, the views and opinions expressed in communication with individuals within the company may not reflect that of the business as a whole.
You can find this, and all issued technical bulletins on the Worcester website at: worcester-bosch.co.uk/tb or worcester-bosch.ie/tb
Worcester, Bosch Group, Cotswold Way, Warndon, Worcester WR4 9SW Technical Services: 0330 123 3366 | technical-advice@uk.bosch.com
figure 4
above.
Description
Distance from openings adjacent to or above
a vertical terminal (i.e., Windows)
Horizontal terminal towards an opposing
terminal (Ref. Figure 6)
Distance from openings below a Vertical
terminal (i.e., Skylight)
Distance required for flues with openings
located nearby.
Horizontal terminal to an opposing flat
surface (Ref. Figure 6)
if terminating at same height. If multiple flues terminate
Unit
50 kW
65 kW
85 kW
100 kW 125 kW 145 kW
mm
1500
1500
2500
2500
mm
1200
1200
2232
2512
mm
600
600
687
792
mm
438
559
687
792
mm
600
600
1278
1613
2500
2500
2930
3355
948
1107
948
1107
2113
2622
7