Tosline F10 Communications With G3 Inverter And T2 Plc - Toshiba G3 Workbook

Applications workbook
Table of Contents

Advertisement

Tosline F10 Communications With G3 Inverter and T2 PLC

Parts:
G3 Inverter
Tosline F10 card for inverter and the included 4 standoffs.
T2 PLC with Tosline F10 master module (MS211)
T-PDS software and programming cable
G3 Settings:
Inverter ID Number = 8
Communication Selection = 2
F10 Command Input = 3
F10 Monitor Output = 15
Command Mode = 3
Frequency Mode = 3
T2 Settings:
I/O Allocation: Perform auto I/O allocation.
Put "Link" into System Information - I/O Allocation - Network Settings TL-F10 CH1.
Set the following MS211 DIP switch ON: DSO (left bank) switch 4. Put all others OFF.
The rotary switches on the front of the MS211 do not affect operation of the network.
Operation:
Use the data monitor in the T-PDS software to view registers LW000-LW031.
LW008: Monitor the frequency of the G3. Displays Hz*100
LW009: Status bit table of G3. See below.
LW010: Electric current output from G3 to motor.
LW011: Output voltage of G3. Displays ten times percent rated voltage.
LW012: Frequency of G3. Sent by T2. Enter as Hz * 100.
LW013: Command bit table of G3: Sent by T2. Turn on bit 0 to run drive. See below.
For additional assistance, please contact Toshiba Adjustable Speed Drive Marketing Dept. at (800) 872-
Defines the first LW register used by the G3
Lets the G3 know that Tosline F10 is being used.
Defines how many LW registers are received by the G3. 3
equals binary 11, therefore 2 registers are being sent.
Defines how many LW resisters are being sent from the G3.
15 equals binary 1111, therefore 4 parameters are output.
Lets the G3 get its command input from Tosline F10.
Lets the G3 gets its frequency from Tosline F10.