34 Electrical installation

Earthing

The PVS800-IS inverter station has a main earthing busbar for container earthing.
Connect the inverter station to the earthing busbar of the MV station. Construct an earthing
electrode for the MV substation according to the local regulations. Lead the copper connection
wire from the MV substation's earthing busbar to the main earthing busbar (MEB) of the
inverter station. The MEB of the inverter station is located on the wall near the exit door.
Check that the inverter station is properly connected to earth.
=MV-SUBSTATION
Earthing electrode
HEA M12/70
=MV
+MEB
=TR
=PVS800-IS
=LV
+MEB

Measuring the insulation resistance of the cabling

Check that the insulation resistances of the external power cables have been measured
according to local regulations. See PVS800-57B hardware manual (3AXD50000048300
[English]).
Frame
+H1-H3
Switchgear
PE
+T1
Transformer
Frame
Frame
+PVS1
H07-V-K 120mm2
Inverter
AC Main
Switch
PE
H07-V-K 120mm2
H07-V-K
120mm2
+EAB
H07-V-K
Aux. power box
16mm2
PE
+H3
Transf. breaker
+PVS2