On To Off Delay; Data Transfer At Rpi; Module Health Diagnostic - Allen-Bradley 1756 Series User Manual

Controllogix digital safety i/o modules
Hide thumbs Also See for 1756 Series:
Table of Contents

Advertisement

Chapter 3
1756-IB16S Input Module Features

Data Transfer at RPI

Module Health Diagnostic

52

On to Off Delay

An input signal is treated as Logic 1 during the On to Off delay time after the
falling edge of the input contact.
The input turns off only if the input contact remains off after the On to Off delay
time has elapsed. This setting helps to prevent rapid changes of the input data due
to contact bounce.
You can delay the On to Off transition by the following times:
• 0 ms
• 1 ms
• 2 ms
• 5 ms
• 10 ms
• 20 ms
• 50 ms
Figure 11 - On to Off Delay
ON
Input Signal
OFF
ON
Safety Input
Network Data
OFF
The safety input module always sends data to the owner-controller at the RPI.
You set the RPI on the Connection page of the Module Properties dialog box in
the Logix Designer application.
Every I/O module has a status indicator on the front of the module that indicates
module health.
For more information on status indicators, see Appendix A,
Module on page
103.
Rockwell Automation Publication 1756-UM013B-EN-P - October 2019