Download Print this page
Belimo Z2050QPT-D Quick Start Manual

Belimo Z2050QPT-D Quick Start Manual

Pressure independent zonetight zone valves (piqcv)

Advertisement

Quick Links

Z2050QPT-D, Pressure Independent ZoneTight
Zone Valves (PIQCV)
Technical Data
Service
chilled, hot water, up to 60% glycol
Flow Characteristic
equal percentage
Controllable Flow Range
75°
Valve Size
0.5 " [15]
End Fitting
NPT female ends
Body
forged brass
Ball
stainless steel
Stem
stainless steel
Seat
Teflon® PTFE
Seat O-ring
EPDM
Characterized Disc
incorporated into the ball
Diaphragm
EPDM
Body Pressure Rating
360 psi
Media Temperature
36°F to 212°F [2°C to 100°C]
Range (Water)
Maximum Allowable
212°F [100°C] *
Operating Temperature
Media Temperature Limit 250°F [121°C] *
Diff. Pressure Range
5 to 50 psi
Close-Off Pressure
200 psi
Valve Accuracy
+/- 5%
Weight
1.8 lb [0.8 kg]
GPM
1.9
Leakage
0%
Servicing
maintenance free
* If temperature exceeds 212°F operating range due to a boiler control failure the valve will safely contain
the hot water but manufacturers product warranty becomes invalid. Valve and actuator replacement is at
the expense of others.
800-543-9038 USA
281354
866-805-7089 CANADA
Application
The PIQCV zone valves with its pressure independent technology are suited
for large commercial buildings where higher close-off and dynamic balancing
is required. Common applications include unit ventilators, fan coil units, VAV
reheat coils, fin tube casing, radiant panels and duct coils. The valve fits in
space restricted areas and can be assembled without the use of tools.
Suitable Actuators
Non-Spring
Z2050QPT-D
CQ
Dimensions (Inches [mm])
E
F
A
B
C
4.90"
4.17" [106] 4.79" [122]
[124.5]
203-791-8396 LATIN AMERICA / CARIBBEAN
Electronic Fail-Safe
CQK
D
B
A
D
E
3.5" [89]
2.44" [62]
1.3" [31.5]
C
F

Advertisement

loading

Summary of Contents for Belimo Z2050QPT-D

  • Page 1 Z2050QPT-D, Pressure Independent ZoneTight Zone Valves (PIQCV) Application The PIQCV zone valves with its pressure independent technology are suited for large commercial buildings where higher close-off and dynamic balancing is required. Common applications include unit ventilators, fan coil units, VAV reheat coils, fin tube casing, radiant panels and duct coils.
  • Page 2 Z2050QPT-D, Pressure Independent ZoneTight Zone Valves (PIQCV) Dimensions (Inches [mm]) 4.90” 4.17” [106] 4.5” [114.3] 3.43” [87] 2.44” [62] 1.3” [31.5] [124.5] 800-543-9038 USA 866-805-7089 CANADA 203-791-8396 LATIN AMERICA / CARIBBEAN...
  • Page 3 CQKB24-SR-RL Modulating, Electronic Fail-Safe, 24 V, for 2 to 10 VDC or 4 to 20 mA Control Signal Technical Data 282498 Power Supply 24 VAC, ±20%, 50/60 Hz, 24 VDC, ±10% Power Consumption Running 2.5 W Power Consumption Holding 0.5 W Transformer Sizing 5 VA (class 2 power source) Electrical Connection...
  • Page 4 CQKB24-SR-RL Modulating, Electronic Fail-Safe, 24 V, for 2 to 10 VDC or 4 to 20 mA Control Signal Wiring Diagrams INSTALLATION NOTES Actuators with appliance cables are numbered. Common Line Volts + Hot Actuators may be connected in parallel. Power consumption and input impedance must be observed.