Wall-Mounted Type (KS Type)

3-13. Removing the Wall Fixture from the Unit

KS2432, KS2432A
Remove and discard the set screws and take off the
wall fixture. (Fig. 3-36)

3-14. Selecting and Making a Hole

KS2432, KS2432A
(1)
Tape the full-scale installation diagram on the
walll at the location selected (KS2432 only.
Not provided for KS2432A.). Make sure the unit
is horizontal, using a level or tape measure.
(Fig. 3-37)
(2)
Before drilling a hole, check that there are no
studs or pipes behind the determined location.
Avoid area where electrical
wiring or conduit is located.
CAUTION
Also take this precaution if
the tubing goes through a
wall at any other location.
(3)
Using a sabre saw, key hole saw or 3-5/32 in.
hole-cutting drill attachment, make a hole in the
wall. The required minimum hole diameter for
these models is 3-3/16 in. (Fig. 3-38)
(4)
Measure the thickness of the wall from the inside
edge to the outside edge and cut PVC pipe at a
slight angle 1/4 in. shorter than the thickness of
the wall. (Fig. 3-39)
(5)
Place the plastic cover over the end of the pipe,
(for indoor side only) and insert in the wall.
(Fig. 3-40)
Wall fixture
Set screws only for transportation
Fig. 3-36
F u ll - s c a le
in s ta ll a ti o
Fig. 3-37
NOTE
Hole should be made at a slight downward slant to the
outdoor side.
Indoor
side
Fig. 3-38
PVC pipe (locally purchased)
Fig. 3-39
INSIDE
Plastic
cover
Fig. 3-40
22
S4359249
1390_T_I
Tape
n d ia g r a m
0940_T_I
Outdoor
side
0066_T_I
Cut at slight angle
0941_T_I
OUTSIDE
Wall
PVC pipe
Slight
angle
0942_K_I