Sanyo C2432A Installation Instructions Manual page 45

Hide thumbs Also See for C2432A:
Table of Contents

Advertisement

To avoid nitrogen entering
CAUTION
the refrigerant system in a
liquid state, the top of the
cylinder must be higher than
the bottom when you pres-
surize the system. Usually,
the cylinder is used in a
vertical standing position.
(Refer to the previous page.)
(4)
Do a leak test of all joints of the tubing (both
indoor and outdoor) and both wide and narrow
service valves. Bubbles indicate a leak. Wipe off
the soap with a clean cloth after a leak test.
(5)
After the system is found to be free of leaks,
relieve the nitrogen pressure by loosening the
charge hose connector at the nitrogen cylinder.
When the system pressure is reduced to normal,
disconnect the hose from the cylinder.
Evacuation
(1)
Attach the charge hose end described in the
preceding steps to the vacuum pump to evacuate
the tubing and indoor unit.
Confirm that the "Lo" knob of the manifold valve
is open. Then, run the vacuum pump. The
operation time for evacuation varies with the
tubing length and capacity of the pump. The
following table shows the amount of time for
evacuation:
Required time for evacuation
when 30 gal/h vacuum pump is used
If tubing length is
less than 50 ft.
45 minutes or more
NOTE
The required time in the above table is calculated
based on the assumption that the ideal (or target)
vacuum condition is around 10 mmHg abs.
(2)
When the desired vacuum is reached, close the
"Lo" knob of the manifold valve and turn off the
vacuum pump.
If tubing length is
longer than 50 ft.
90 minutes or more
45
Manifold valve
Pressure
Lo
Hi
gauge
Vacuum pump
Outdoor unit
Service
valve
*
Narrow
tube
Indoor unit
3-way valve is used for 3632 type.
*
Fig. 9-3
Manifold valve
Vacuum
Lo
gauge
Cap
Narrow tube
Wide tube
Fig. 9-4
S4179694
Wide tube
1391_C_I
Hi
Vacuum pump
0540_C_I

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents