Installation
4.1.2 Mounting Requirements
Mount the inverter vertically or tilted backward by max 15°. In order to facilitate the heat dissipation
of the inverter.
The wrong installation mode causes the inverter to be damaged or unable to
NOTICE
work properly.
≤15°
Lean back ≤15°
Upright
4.1.3 Installation Space Requirements
To ensure the inverter normally and easy to operate, there are requirements on available spaces of the
inverter, e.g. to keep enough clearance. Refer to the following figures.
≥600
≥600
600mm
Installation along the same line for multiple inverter
(
This is only an example of the Fan cooling series
14
Three phase Grid-tied PV String Inverter User Manual
Horizontally
Upside-down
Above: 600mm
Below: 600mm
Front: 1000mm
Both sides: 600mm
600mm
.)
Three phase Grid-tied PV String Inverter User Manual
Installation perspective schematic
�
294
7
Bracket plane size drawing
Installation
51
354
29
8
170.5
Unit: mm
15