PrimeVOLT PV 5KTL-D3/G2 User Manual page 16

Three phase grid-tied pv string inverter
Hide thumbs Also See for PV 5KTL-D3/G2:
Table of Contents

Advertisement

User Interface
Table 7-1 LED status descriptions
LED status
Descriptions
Blue led blink
Standby or startup state
slowly 1times/s
(not connected to the grid)
Blue on
Grid-tied status
Green on
Power limited status
Warning
COM
E-Today
E-Total
Meter
Figure 7-2 LCD Screen
COM
When WIFI/GPRS/Bluetooth is transferring data, icon
the icon will be off after 10s. When RS485 is transferring data, icon
transmission, the icon will be off after 10s.
Warning
When warning is triggered, icon will be illuminated: from left to right the first bit could beA/ B/ C,
it stands for warning type, and the second bit is warning code, please refer to warning code in table
for details.
Date
When external communications is normal and time zone is set correctly, the built-in clock of
inverter will be synchronized with server's time.Without external communications, it is recommended
to use the mobile app to set up time through connecting bluetooth to the inverter.
Status
Icon
stands for PV strings,when inverter is standby status, MPPT voltage of the PV string
will be displayed in Meter zone.
Icon
stands for grid,when voltage and frequency of power grid is in normal range, the
icon keeps on, or else, it blinks; when there is no voltage, the icon will be off.
Icon
stands for energy flow,when inverter is in normal status, the icon will be on, or else it
will be off.
30
Three phase Grid-tied PV String Inverter User Manual
LED status
Descriptions
Red led blink slowly 1times/s
Output side fault
Red led blink quikly 1times/0.25s Iutput side fault
Red led on
System internal fault
Red/Green/Blue light
Burning code(Master/Slave)
alternately (1 color /0.25s)
Control power set up (lasts 1s)
Date
Status
Power
A
B
C
Output
will be ON, while no data transmission,
will be ON, while no data
Three phase Grid-tied PV String Inverter User Manual
Meter
Normal status: today and total energy, MPPT
voltage and current are showed in turn.
Standby status: counter down value before
inverter start up.
Any status: setting parameters via APP, the
screen keep for 5 seconds.
Normal status: output power, grid voltage
and current are showed in turn.
Warning Table
Status
Details
Warning code
Grid over voltage
A0
Grid under voltage
A1
Red led
Grid absent
A2
blink
Grid over frequency
A3
(slowly)
Grid under frequency
A4
1s every
times
Grid unbalance
A6
A7
Grid over mean voltage
PV over voltage
B0
Insulation resistance abnormal B1
Leakage current abnormal
B2
Strings abnormal
B3
PV under voltage PV
B4
Red led
Control power abnormal
C0
blink
(slowly)
Electric arc abnormal
C1
0.25s
DC bias current abnormal
C2
every
times
Inverter relay abnormal
C3
Inverter over temperature
C5
Leakage current HCT abnormal C6
System fault
C7
DC link voltage unbalance
C9
User Interface
E-Today
E-Total
Power
Status
Details
Warning code
DC-link over voltage
CA
Internal communication error
CB
Software version incompatibility
CC
EEPROM fault
CD
Red led
on
Sampling inconsistency
CE
Invert circuit abnormal
CF
Boost circuit abnormal
CG
Data logger lost
CH
Meter lost
CJ
Fan abnormal
C8
/
Remote off
CN
Note: If you select a machine with a LCD screen,the warning
code will be displayed on the LCD screen.Non-lcd screen models
need to enter the app to view the corresponding warning code.
31