Electricity Connection

5.3 DC Connection

PV modules generate electric energy when exposed to sunlight and can create
an electrical shock hazard. Therefore, when connecting the PV modules,
shield them with opaque cloth and ensure that DC switches are OFF.
To avoid electric shock, don't touch the charge part and connect the terminals carefully.
DANGER
Before connecting power cables,ensure the AC/DC switches are OFF.
When the inverter is grid-tied, it is not allowed to operate the PV strings ,
only allow after the inverter enters in shutdown mode.
PV modules connected in series in each PV string must be of the same specifications.
The maximum open-circuit voltage of each PV string must be always lower
than or equal to its permitted range.
The maximum short circuit current of each PV string must be always lower
WARNING
than or equal to its permitted range.
Ensure that the positive and negative terminals of each PV strings connected to the
inverter are correct.
The positive or negative terminals of PV strings can't be connected with short circuit.
The total output power of all PV strings can't exceed the maximum input power of the inverter.
The positive and negative terminals of PV modules can't connect to PE wire(GND) ,
otherwise, the inverter will be damaged.
Ensure that the voltage of each PV string doesn't exceed 1100V under any circumstances.
NOTICE
Input voltage ranges from 1000V to 1100V, the inverter in standby status.
When the voltage is restored to the operating voltage range 160V to 1000V of
the MPPT , the inverter returns to normal status.
5.3.1 Preparation
Different
PV module input configuration module table(All PV strings are grouped into corresponding groups
and connected to inverter)
Inverter module
PV input configuration
PV 5KTL-D3/G2, PV 6KTL-D3/G2
PV strings
PV 8KTL-D3/G2, PV 10KTL-D3/G2P
PV strings
PV strings
PV 12KTL-D3/G2,PV 15KTL-D3/G2
PV strings
PV 10KTL-D3/G2P, PV 12KTL-D3/G2P,
PV strings
PV 15KTL-D3/G2P
PV strings
PV 17KTL-D3/G2, PV 20KTL-D3/G2
PV strings
PV strings
PV strings
PV 22KTL-D3/G2,PV 25KTL-D3/G2
All PV strings are connected into four groups
22
Three phase Grid-tied PV String Inverter User Manual
circuit<15A, All PV strings are connected into a group
circuit<12A, All PV strings are connected into two groups
circuit>12A, All PV strings are connected into a group
circuit≤15A, All PV strings are connected into two groups
circuit≤15A,All PV strings are connected into two groups
circuit>15A, All PV strings are connected into a group
circuit<12A, All PV strings are connected into four groups
circuit≥12A≤15A, All PV strings are connected into three groups
circuit>15A, All PV strings are connected into two groups
Three phase Grid-tied PV String Inverter User Manual
Before connecting the PV input to the inverter, ensure that the package meets the following
electrical specifications.
Inverter module Limit of each input open-circuit voltage
All
1100V
Open-circuit voltage altitude derating curve of the inverter as shown in the following figure.
1100V
950V
850V
2000m
Open-circuit voltage altitude derating curve of the inverter
To ensure that the inverter reaches the
NOTE
use the connector provided by supply.
Electricity Connection
Maximum allowable input terminal current
20A
Elevation(m)
3000m
4000m
enclosure
of IP65, it can only
23