Connecting Device To The Server - Siemens SIMATIC HMI Industrial Thin Client ITC1200 Operating Instructions Manual

Hmi device
Table of Contents

Advertisement

Installing and connecting the device
3.4 Connecting the device
Safe power supply
NOTICE
Device malfunction
If the supply voltage is outside the specified range, device malfunctions cannot be ruled
out.
Use only 24 VDC power supply units with safe electrical isolation in accordance with IEC
60364-4-41 or HD 60364-4-41, for example, to SELV / PELV standard.
Applies to non-isolated plant configurations: Connect the "GND" terminal of the 24 VDC
power supply to the equipotential bonding. You should always select a central point of
termination.
See also
Interfaces (Page 12)
3.4.4

Connecting device to the server

Configuration graphic
The following figure shows the connection between the device and the server via
PROFINET/Ethernet.
Procedure
1. Connect the PROFINET/Ethernet cable
See also
Interfaces (Page 12)
30
to a server.
Industrial Thin Client ITC1200, ITC1500, ITC1900, ITC2200
Operating Instructions, 04/2013, A5E03474888-02