Home Automation (WMP) – Samsung NASA
TM
Intesis

8. Error codes for Indoor and Outdoor Units

This list contains all possible values shown in Modbus register for "Error Code" for each indoor unit and outdoor
unit.
It must be taken into account that Outdoor Units are only able to reflect a single error for each indoor / outdoor unit
in the system. Thus, a unit having two or more active errors from that list will only report a single error code – the
one of the first error that has been detected.
Error
Description
Code
101
Indoor unit communication error. Indoor unit can not receive any data from outdoor unit.
102
Communication error between indoor unit and outdoor unit. Displayed in indoor unit.
108
Error due to repeated address setting (When 2 or more devices has same address within the
Communication error between Hydro unit HT(Main PBA) and Control kit PBA(Detection from
110
the Control kit)
121
Error on indoor temperature sensor of indoor unit (Short or Open)
122
Error on EVA IN sensor of indoor unit (Short or Open)
123
Error on EVA OUT sensor of indoor unit (Short or Open)
128
EVA IN temperature sensor of indoor unit is detached from EVA IN pipe
129
EVA OUT temperature sensor of indoor unit is detached from EVA OUT pipe
130
Heat exchanger in/out sensors of indoor unit are detached
135
RPM feedback error of indoor unit's cleaning fan
151
Error due to opened EEV of indoor unit (2nd detection)
152
Error due to closed EEV of indoor unit (2nd detection)
153
Error on floating switch of indoor unit (2nd detection)
154
RPM feedback error of indoor unit
Mixed operation mode error of indoor unit; When outdoor unit is getting ready to operate in
161
cooling (or heating) and some of the indoor unit is trying to operate in heating (or cooling) mode
162
EEPROM error of MICOM (Physical problem of parts/circuit)
Indoor unit's remote controller option input is Incorrect or missing. Outdoor unit EEPROM data
163
error
180
Simultaneous opening of cooling/heating MCU SOL V/V (1st detection)
181
Simultaneous opening of cooling/heating MCU SOL V/V (2nd detection)
185
Cross wiring error between communication and power cable of indoor unit
186
Connection error or problem on SPi
No temperature changes in EVA IN during pipe inspection or changes in temperature indoor
190
unit with wrong address
No temperature changes in EVA OUT during pipe inspection or changes in temperature is seen
191
in indoor unit with wrong address
198
Error due to disconnected thermal fuse of indoor unit
Communication error between indoor and outdoor units (installation number setting error,
201
repeated indoor unit address, indoor unit communication cable error)
Communication error between indoor and outdoor units (Communication error on all indoor
202
unit, outdoor unit communication cable error)
203
Communication error between main and sub outdoor units
205
Communication error on all PBA within the outdoor unit C-Box, communication cable error
E206-C001: HUB PBA communication error / E206-C002: FAN PBA communication errorE206-
206
C003:INV1 PBA communication error / E206-C004: INV2 PBA communication error
211
When single indoor unit uses 2 MCU ports that are not in series.
If the rotary switch (on the MCU) for address setting of the indoor unit has 3 or more of the
212
same address
© HMS Industrial Networks S.L.U. - All rights reserved
This information is subject to change without notice
User Manual r1.0 EN