Power Device; Connect To Samsung Nasa Vrf Installation; Connection To Home Automation (Wmp); Connection To Pc (Configuration Tool) - HMS Networks Intesis WMP User Manual

Table of Contents

Advertisement

Home Automation (WMP) – Samsung NASA
TM
Intesis

3.1. Power device

The first step to perform is to power up the device. To do so, a power supply working with any of the voltage range
allowed is needed (check
WARNING! To avoid earth loops that can damage the gateway, and/or any other equipment connected to it, we
strongly recommend:
The use of DC power supplies, floating or with the negative terminal connected to earth. Never use a
DC power supply with the positive terminal connected to earth.
The use of AC power supplies only if they are floating and not powering any other device.

3.2. Connect to Samsung NASA VRF installation

Use the PortA connector in the top corner of the Intesis device in order to connect Samsung NASA bus to the Intesis.
Remember to follow all safety precautions indicated by Samsung.
To properly communicate with the Intesis, take into account the following considerations:
-
Samsung NASA AC network allows for both automatic and manual addressing. Manual addressing of
both indoor and outdoor units must be setup by Samsung installer in order that Intesis
communicates properly. Manual addressing is setup by means of DIP switches in outdoor unit and using
the remote controller or DIP switches in the indoor unit.
Samsung NASA indoor units need to be configured to accept 'central control'. To do so, they need to
-
be configured with so-called 'installation option code' in which segment 5 of this code needs to be set to
value '1' to allow central control.

3.3. Connection to Home Automation (WMP)

The gateways Ethernet port connection is used for the Home Automation (WMP) TCP communication. Connect the
communication cable coming from the network hub or switch to the Ethernet port of Intesis. The cable to be used
shall be a straight Ethernet UTP/FTP CAT5 cable.
TCP port to use (default 3310) and keep alive period must be configured.
IP settings of the gateway (DHCP status, own IP, netmask and default gateway) must be configured as well.

3.4. Connection to PC (Configuration tool)

This action allows the user to have access to configuration and monitoring of the device (more information can be
found in the configuration tool User Manual). Two methods to connect to the PC can be used:
Ethernet: Using the Ethernet port of Intesis.
USB: Using the console port of Intesis, connect a USB cable from the console port to the PC.
© HMS Industrial Networks S.L.U. - All rights reserved
This information is subject to change without notice
5 E
& M
LECTRICAL
ECHANICAL
F
). Once connected the ON led will turn on.
EATURES
User Manual r1.0 EN
URL
https://www.intesis.com
10 / 25

Advertisement

Table of Contents
loading

Table of Contents