Nice HySecurity StrongArmPark DC Series Installation Instructions page 4

Articulating arm

Advertisement

5. Connect the one wire lead to the 24VDC power supply terminal.
See wiring illustrations on page 2.
6. Connect the other wire lead to the NO terminal on User Relay 2.
7. Turn on both AC and DC power switches. Arm will cycle to search
for the target home position.
8. When the arm has stopped moving, access the Installer Menu.
9. Set the User Relay 2 logic function to one of the following:
R2 "27": LED lights remain on throughout arm travel and turn off when
open limit is reached.
R2 "28": LED lights flash throughout arm travel and turn off when open limit
is reached.
NOTE: In the event of AC power loss, either selection (27 or 28) turns off the
lights which preserves battery life.
RELAY 2: INSTALLER MENU FLOW DIAGRAM
Status Display
GATE CLOSED
Press MENU twice
at a Run Mode static
display.
User Menu
CT 0 (OFF)
To access the Installer Menu,
press and hold RESET & OPEN,
and then release them.
www.hysecurity.com
© 2017
Press Next, until "R2 0 DISABLED" appears.
Installer Menu
R2 0 DISABLED
Press SELECT. The "R2"
characters blink.
Installer Menu
R2 28 FLASH AC
Press Next until ""R2 28 FLASH AC" appears (Or
choose R2 "27" if you don't want the lights to flash.)
Press SELECT again to set the User Relay 2 function.
COM
COM
COM
COM
COM
COM
COM
COM
STOP
OPEN
CLOSE
OPEN
P ARTIAL
EYE
OPEN
EYE
CLOSE
EXIT
LOOP
BLOCK
EXIT
IN OBS
LOOP
OUT OBS
LOOP
CENTER
LOOP
EDGE
EYE
COM
+ 24 V
EMERG
OPEN
SHOW
LEDs
R2 28 FLASH AC
RELAY 2 LOGIC
OPEN
CLOSE
PREV
NEXT
Page 4
See
CAUTION
USER RELAY 2
Solid state
STOP
MENU
RESET
SELECT
P/N MX3114 D0584 Rev C