Download Print this page

HUBBELL LIGHTING Dual-Lite EV Series Quick Start Manual

Twin-head led emergency lighting unit

Advertisement

Quick Links

Installing the Unit: Final Assembly
1. Align housing slots over tabs on backplate.
2. Pivot housing and snap closed.
3. Aim the lamps. Do not press on the lenses.
SERVICE/MAINTENANCE
Service / Maintenance
Maintenance
This emergency lighting unit should be tested and maintained in accordance with National Electrical Code and NFPA 101 Life Safety
Code requirements. It is recommended that emergency light fixtures be tested for 30 seconds once a month and for 90 minutes once a
year.
Taking A Unit Out Of Service
If a unit is to be deliberately taken out of service for an extended period, the battery lead connector should be disconnected from the
charger circuit board and insulated so that the battery will go into storage in a fully charged condition.
Replacing The Battery
1. De-energize the AC power.
2. Disengage the housing cover from the backplate.
3. Disconnect the battery leads from the charger circuit board.
4. Remove the battery from the clips inside the cover.
5. Replace with a new battery (see unit model label for correct part number) and reconnect leads.
6. Reassemble cover to backplate.
Replacing LED Lamps
The LED lamps inside the unit are not replaceable or field serviceable. Please see dual-lite.com for further assistance.
Troubleshooting
Emergency circuit does not work
• Batteries are shipped uncharged and disconnected. Connect battery leads and charge 24 hours before testing.
• Make sure the charger board and test button/light pipe are properly seated and aligned.
• Check wiring connections.
RECYCLING INFORMATION
All steel, aluminum and thermoplastic parts are recyclable.
NOTICE: Emergency units contain rechargeable batteries which
must be recycled or disposed of properly.
Hubbell Lighting, Inc. Life Safety Products • www.dual-lite.com
Copyright
Hubbell Lighting, Inc., All Rights Reserved • Specifications subject to change without notice. • Printed in U.S.A.
©
93033106_B 06/17
INSTALLATION
93034799
IMPORTANT SAFEGUARDS
READ AND FOLLOW ALL SAFETY
1.
Do not use outdoors.
2.
Do not let power supply cords touch hot surfaces.
3.
Do not mount near gas or electric heaters.
4.
Equipment should be mounted in locations and at heights where it will not readily be subject
to tampering by unauthorized personnel.
5.
The use of accessory equipment not authorized by the manufacturer may cause an
unsafe condition.
6.
Do not use this equipment for other than its intended purpose.
7.
Servicing of this equipment should be performed by qualified service personnel.
8.
Test cycling: the Life Safety Code (NFPA 101) requires testing of emergency lighting units once a month for a
minimum of 30 seconds, and once a year for a minimum of 90 minutes.
•SEE UNIT LABEL FOR ADDITIONAL MODEL SPECIFICATIONS
•SAVE THESE INSTRUCTIONS FOR USE BY OWNER/OCCUPANT
WARNING – This product contains chemicals known to the State of California to cause cancer, birth
defects and/or other reproductive harm. Thoroughly wash hands after installing, handling, cleaning,
or otherwise touching this product.
Emergency Lighting Equipment For Use in Damp Locations
93034795
Damp location listed units are suitable for installation in:
93034797
1. Interior locations subject to modreate degrees of moisture, such as some basements, some barns, some cold storage
93034799
warehouses, and the like.
93034800
93035762
2. Partially protected locations under canopies, marquees, roofed open porches and the like.
Twin-Head LED Emergency Lighting Unit
Standard, Remote, and Spectron
Installation, Opperation, and Service Instructions
When using electrical equipment, basic safety precautions should
always be followed including the following.
INSTRUCTIONS
INSTALLER:
EV Series
®
Equipped Models
93034800

Advertisement

loading

Summary of Contents for HUBBELL LIGHTING Dual-Lite EV Series

  • Page 1 2. Partially protected locations under canopies, marquees, roofed open porches and the like. Hubbell Lighting, Inc. Life Safety Products • www.dual-lite.com Copyright Hubbell Lighting, Inc., All Rights Reserved • Specifications subject to change without notice. • Printed in U.S.A. © 93033106_B 06/17...
  • Page 2 INSTALLATION INSTALLATION INSTALLATION All EV units are shipped by default with the charger circuit board jumper in the “remote lampheads disabled” position, This unit is designed to be mounted on a wall or ceiling. Provide standard units with a single unswitched supply from a 120VAC, 240VAC, as shown in Figure 1.

This manual is also suitable for:

Dual-lite ev2di