Download Print this page
HUBBELL LIGHTING Dual Lite EZ-2 Series Installation, Operation And Service Instructions

HUBBELL LIGHTING Dual Lite EZ-2 Series Installation, Operation And Service Instructions

Twin-head emergency lighting unit, standard and spectron equipped models

Advertisement

Quick Links

Taking A Unit Out Of Service
If a unit is to be deliberately taken out of service for an extended period, the positive (+) battery lead should be
disconnected from the charger/transfer module and insulated so that the battery will go into storage in a fully charged
condition. See Fig. 3 or Fig. 4.
Fig. 1
SURFACE WIRING
BREAKOUT
CHASSIS RETAINING
SCREWS
93027736
LED DISPLAY
Fig. 4
CONNECTOR
PIN 1 - BLACK
LAMPS (—)
BATTERY (—)
TEST SWITCH
BATTERY (+)
Replacing A Battery
1.
De-energize the AC power.
2.
Loosen the (2) chassis retaining screws (Fig. 1).
3.
Open the unit and disconnect the battery leads.
4.
Release battery retaining strap, and swing to the side.
5.
Remove the battery.
6.
Replace with a new battery (see unit model label for correct part number).
7.
Reassemble the unit.
Fig. 5
Fig. 6
LENS
93021606
Replacing An Emergency Lamp
1.
To remove the lamp assembly from the lamp housing, place a screwdriver into the slot (Fig. 5), and pry
the lamp assembly out.
2.
Insert a screwdriver into the lens slot (Fig. 6) and pry the lens from the reflector assembly.
3.
Remove the defective bulb (Fig. 7). Insert a new bulb into the reflector by aligning bulb base with socket and
pushing lamp firmly into socket.
4.
Reassemble the lamp:
a.
align the small "key", located between the anti-rotation tabs on the reflector assembly, with the
"keyway" adjacent to the ribbed area on the edge of the lens. (Fig. 7).
b.
press the lens into the reflector assembly.
5.
Rejoin lamp assembly to lamp housing:
a.
orient the lamp assembly's anti-rotation tabs to the top of the lamp housing.
b.
set the bottom of the lamp assembly into the housing and dress wires neatly into the housing cavity.
c.
insert a screwdriver into the slot (Fig. 5) and lever the lamp assembly into the housing.
Hubbell Lighting, Inc. Life Safety Products • www.dual-lite.com
Copyright
Hubbell Lighting, Inc., All Rights Reserved • Specifications subject to change without notice. • Printed in U.S.A.
©
SERVICE
Fig. 3
LAMP
TERMINALS (-)
BATTERY(+)
VOLT METER (-) [-V OPTION ONLY]
BATTERY (-)
LAMP
TERMINALS (+)
VOLT METER (+) [-V OPTION ONLY]
RECYCLING INFORMATION
All steel, aluminum and thermoplastic parts
are recyclable.
1300738
NOTICE: Emergency units contain
LAMPS (+)
rechargeable batteries which must be
recycled or disposed of properly.
Fig. 7
TO REMOVE LAMP, GRASP FIRMLY
93021607
AND PULL STRAIGHT UP
ANTI-ROTATION
TABS
REFLECTOR
ASSEMBLY
RIBBED LENS AREA
93021781 B 3/10
1300671

IMPORTANT SAFEGUARDS

When using electrical equipment, basic safety precautions should
READ AND FOLLOW ALL SAFETY
1. Do not use outdoors.
2. Do not let power supply cords touch hot surfaces.
3. Do not mount near gas or electric heaters.
4. Equipment should be mounted in locations and at heights where it will not readily be subject
to tampering by unauthorized personnel.
5. The use of accessory equipment not authorized by the manufacturer may cause an
unsafe condition.
6. Do not use this equipment for other than its intended purpose.
7. Servicing of this equipment should be performed by qualified service personnel.
8. Test cycling: the Life Safety Code (NFPA 101) requires testing of emergency lighting units
93021608
once a month for a minimum of 30 seconds, and once a year for a minimum of 90 minutes.
•SEE UNIT LABEL FOR ADDITIONAL MODEL SPECIFICATIONS
•SAVE THESE INSTRUCTIONS FOR USE BY OWNER/OCCUPANT
WARNING – This product contains chemicals known to the State of California to cause cancer,
birth defects and/or other reproductive harm. Thoroughly wash hands after installing, handling,
cleaning, or otherwise touching this product.
1300671
1300738
93021606
93021607
93021608
93027736
Twin-Head Emergency Lighting Unit
Standard and Spectron® Equipped Models
Installation, Operation and Service Instructions
always be followed including the following.
INSTRUCTIONS
INSTALLER:
EZ-2 Series

Advertisement

loading

Summary of Contents for HUBBELL LIGHTING Dual Lite EZ-2 Series

  • Page 1: Important Safeguards

    (Fig. 5) and lever the lamp assembly into the housing. 1300671 1300738 93021606 93021607 93021608 93027736 Hubbell Lighting, Inc. Life Safety Products • www.dual-lite.com Copyright Hubbell Lighting, Inc., All Rights Reserved • Specifications subject to change without notice. • Printed in U.S.A. © 93021781 B 3/10...
  • Page 2 INSTALLATION OPERATION General Instructions When the AC circuit is initially energized, the status lamp on standard units will typically stay at full brilliance for This unit is designed for surface mounting on a wall with or without an outlet box. KO’s provided for single gang, several hours before fading to a “dim”...