Operating Range - York YVAG012 Operation & Maintenance Manual

Dc inverter air-cooled chiller and heat pump
Table of Contents

Advertisement

OPERATING RANGE

Voltage Range
The maximum fluctuation range of supply voltage is ±10%
Three-phase electric phase unbalance rate should be less than 2%.
Temperature range
Project
Relative humidity
Wire controller using the environment
temperature
The unit running environment
temperature range
Chilled water temperature range
(Leaving water temperature)
Chilled water temperature range
(Enter water temperature)
Please note that
The return water temperature control is default by the unit controller, and return water temperature
control is recommended.
The above data are obtained in the laboratory, the practical use there will be deviation affected by
the installation position and so on.
For applications with temperature below -25℃, please consult YORK company.
Applicable Medium
The standard design applicable medium of the unit is purified water. Please consult YORK Company for special
medium such as glycol antifreeze fluid.
Altitude
No more than 2000m
Wind side external static pressure
No more than 30Pa
JOHNSON CONTROLS
Cooke Industries - Phone: +64 9 579 2185
TABLE 1-Temperature range(YVAG012~040)
012~018
<90%,No lon
-10℃~55℃
Cooling -5℃~48℃
Heating -20℃~43℃
Cooling 5℃~25℃
Heating 30℃~52℃
Cooling 10℃~30℃
Heating 25℃~47℃
Email: sales@cookeindustries.co.nz
FORM NO.: 6U5M-A11M-NB-EN
020~040
<90%,No lon
-10℃~55℃
Cooling -5℃~48℃
Heating -25℃~43℃
Cooling 5℃~25℃
Heating 30℃~58℃
Cooling 10℃~30℃
Heating 25℃~53℃
Web: www.cookeindustries.co.nz
8