York YVAG012 Operation & Maintenance Manual page 30

Dc inverter air-cooled chiller and heat pump
Table of Contents

Advertisement

Unit Power Supply
1. Unit Power Supply
MODEL TYPE
POWER SUPPLY
MAXIMUM OPERATING CURRENT
RECOMMENDED WIRE DIAMETER
RECOMMENDED BREAKER
(EARTH LEAKAGE PROTECTOR)
Notes:
1.
Cable selection specification above is suitable for the conditions where ambient temperature is under 40℃,
local regulations should be referred to for practice.
2.
Leakage protector must be deployed, and reliable ground connection should be conducted on site.
3.
For any discrepancy on site, like capacitance decreasing, refer to IEC standards and requirements by cable
manufacturers for selection.
4.
Only copper conductor can be applied as power supply cable and ZR-RVV type cable is recommended.
2. System Power Supply Distribution
FIGURE 31 – SYSTEM POWER SUPPLY DISTRIBUTION DIAGRAM (012~018)
JOHNSON CONTROLS
Cooke Industries - Phone: +64 9 579 2185
TABLE 9 – POWER SUPPLY CABLE SPECIFICATION
012
014
016
220V~50Hz
24A
33A
33A
4mm2
6mm2
6mm2
C 型
C 型
C 型
32A 2P
40A 2P
40A 2P
Email: sales@cookeindustries.co.nz
FORM NO.: 6U5M-A11M-NB-EN
018
020/022
025
380V /400V 3N~50Hz
36A
17A
19A
6mm2
4mm2
6mm2
C 型
C 型
C 型
50A 2P
25A 4P
25A 4P
Web: www.cookeindustries.co.nz
028/033
040
21A
29A
6mm2
6mm2
C 型
CD 型
32A 4P
40A 4P
30