S
p
y t
ci
l
i
i
m
Micro
INSTRUCTION MANUAL: 32 Device,4 Zone Addressable Fire Alarm Panel
ADDRESSABLE
FIRE ALARM PANEL
Specifications
Electrical Specifications
ELECTRICAL DESCRIPTION
MAINS VOLTAGE
BATTERY VOLTAGE
CHARGER SIZE
LOOP VOLTAGE
AUXILIARY FIRE OUTPUT
FAULT OUTPUT
NUMBER OF ZONES
MAXIMUM ZONE CAPACITY
SOUNDER ALARM OUTPUTS
MAINS FAILED CURRENT (BUZZER ON)
MAINS FAILED CURRENT (BUZZER OFF)
MAXIMUM LOOP RESISTANCE
MAXIMUM LOOP CAPACITANCE
MAXIMUM VOLTAGE PICKUP ALLOWED
LOOP SHORT CIRCUIT PROTECTION
CHARGER VOLTAGE
CHARGER SHORT CIRCUIT PROTECTION
Enclosure Specifications
DESCRIPTION
ENCLOSURE SIZE
TOP CABLE ENTRIES
BOTTOM CABLE ENTRIES
REAR CABLE ENTRIES
Fuse Ratings
FUSE NO
DESCRIPTION
FS6
Charger Fuse
FS5
Battery Fuse
INLET FUSE
Mains Protection Fuse
Approved Document No: GLT.MAN-129
Issue : 1.0
Author: NRPJ
VALUE
230V AC +/- 10% @ 50/60 Hz
24V DC (2 X 12V,2AH SLA BATTERY)
1 AMP
27V DC NOMINAL (+9 volt data)
1 x RELAY SELV (1A MAX)
1 x RELAY SELV (1A MAX )
4
8 DEVICES PER ZONE
LOOP POWERED SOUNDERS ONLY
39mA
37mA
25 ohms
0.3μF
50mV
540mA
28.3V @ 22-24
Batteries less than 20V
VALUE
355 x 275 x 70 mm
5 x 19mm KNOCKOUT ENTRIES
NONE
NONE
RATING
2.0A Fast Blow 5 x 20mm glass
800mA Fast Blow 5 x 20mm glass
2A Quick Blow HBC 5 x 20mm ceramic
Date: 11/04/2008
o
C (NO BATTERY)
PAGE 24
Need help?
Do you have a question about the Simplicity Micro and is the answer not in the manual?
Questions and answers