Installation instruction for multiple entry power connection with junction box. For use with all nVent RAYCHEM BTV-, QTVR-, XTV-, KTV- and VPL-heat ing cables. WARNING: To prevent elec tri cal shock, short cir cuit or arc ing, this prod uct must be in stalled cor rect ly and water ingress must be avoid ed before and during the in stal la tion.
Page 5
РУССКИЙ ТС RU C-BE.ИМ43.В.01712 Ex e IIC Gb U Ex tb IIIC Db U Ex e mb IIC Gb U Ex tb mb IIIC Db U Ta -55°C…+56°C IP66 Максимальная температура трубы: Тип нагревателя постоянно периодически при выкл.питании суммарно 1000 ч 65°C 85°C –...
Page 6
BTV, QTVR, XTV, KTV 45° 600 mm 45° 500 mm 600 mm 6 | nVent.com...
Page 13
BTV, QTVR, XTV, KTV, VPL ENGLISH RUSSKIJ Remove the tubes and dispose of Snät´ napravläüwie truboçki i them in the core sealer plastic bag. pomestit´ ix v plastikovyj paket iz-pod uzla izoläcii mednyx Ωil greüwego kabelä. BTV, QTVR, XTV, KTV, VPL 12 - 13 mm 12 - 13 mm nVent.com | 13...
Page 18
BTV, QTVR, XTV, KTV, VPL ENGLISH RUSSKIJ Install power cable and gland. Pull in Podvesti silovoj kabel´ i ustano- power and ground wires, strip off 13 mm vit´ kabel´nyj sal´nik. Propustit´ of insulation and terminate. Connect silovye жи лы, zazemläüwuü Ωilu earth plate to ground according to local kabelä, snät´...