Functions
3.9 Thermal Overload Protection (49)
Settings Menu
CONFIGURATION > FUNCTION CONFIG
Parameter
Gn Thermal O/L
CONFIGURATION > CURRENT PROT'N> THERMAL O/L
Parameter
Gn 49 Element
Gn 49 Setting
Gn 49 TauH
Gn Capacity Alarm
Gn Capacity Alarm
Setting
Gn Stored Thermal
Level
Gn Initial Thermal
Level
11
Gn TauC
Information List
Input/Output
Matrix
Inhibit 49
Reset Thermal Level Reset Thermal Level Input
49 Alarm
49 Trip
49 Reclose Inhibit
11
This setting is only available for dual powered 7SR45 Argus Relay variants
74
Setting Options
Disabled
Enabled
Setting Options
Disabled
Enabled
0.20 ⋅ I
to 1.50 ⋅ I
rated
rated
Δ 0.01 ⋅ I
rated
1.0 m to 300.0 m
Δ 0.5 m
Disabled
Enabled
50 % to 100 %
Δ 1 %
Initial Level
Previous Level
0 % to 40 %
Δ 5%
1.0 ⋅ TauH to 6.0 ⋅ TauH
Δ 0.5 ⋅ TauH
User Logic
Type
Inhibit 49
Input
49 Alarm
Output
49 Trip
Output
49 Reclose Inhibit
Output
11
Settings
Default
Gn1
Disabled
Settings
Default
Gn1
Disabled
1 ⋅ I
rated
45.0 m
Disabled
50 %
Initial Level
0 %
1.0 ⋅ TauH
IEC 103
Y
Y
Y
Y
C53000-G7040-C101-2, Edition 09.2020
Gn2
Gn2
Modbus RTU
Y
Y
Y