Parameters
IE / E
Prot'n Healthy
5
Low Battery
5
IRF
Local mode
Remote mode
Out of Service mode
BI1 Operated
BI2 Operated
BI3 Operated
BI4 Operated
Reclose Inhibit
For more details on Binary Outputs, refer to
User-Programmable LED Operations
The 4 user-programmable LEDs can be configured as Self Reset or Hand Reset (default). This is configured
under OUTPUT CONFIG > LED CONFIG.
Parameters
L4
L5
L6
L7
If the LED is configured as Self Reset, then it is turned ON when the function is active and turned OFF when
function resets. In case the device goes to sleep when the LED was ON, then on device wakeup the LED
remains turned ON as long as the configured function is still active.
If the LED is configured as Hand Reset, then the LED is turned ON when the function is active. The LED
remains ON even after the configured function resets. In case the device goes to sleep when the LED was
turned ON, then on device wakeup the LED remains turned ON irrespective of the configured function status.
The LED can only be reset by pressing TEST/RESET▶ key, BI - Rst LEDs & O/Ps function and through Modbus
or IEC103 commands.

Local Flag

2.1.5
Local flag is an electromechanical bi-stable flag fitted in the front fascia to indicate the trip condition. The
status of the flag is GREEN in normal operation and turns RED during the trip condition.
NOTE
i
i
The auxiliary voltage or phase currents provide the energy required to show the trip indication.
The flag indicates a trip indication when any protection function operates or any binary inputs are mapped
to a trip pulse output.
The trip indication is retained even in the absence of auxiliary voltage and phase currents.
The trip indication can be reset with any power mode by pressing the TEST/RESET▶ key. Refer to the
Modes of Operation chapter in the 7SR45 Operating Manual.
Reyrolle, 7SR45, Device Manual
C53000-G7040-C101-2, Edition 09.2020
Description
Phase E tripped
Protection healthy
Battery volts low indication
Internal relay failure
Local mode
Remote mode
Out of service mode
BI1 operated
BI2 operated
BI3 operated
BI4 operated
Interlock for reclose of CB after 49 trip
2.3 Binary Outputs
Description
L4 self reset or hand reset
L5 self reset or hand reset
L6 self reset or hand reset
L7 self reset or hand reset
LED Default Value
L7
X
X
X
.
LED Default Value
0 (hand reset)
0 (hand reset)
0 (hand reset)
0 (hand reset)
Device Functionality
2.1 Front Fascia
23