Siemens Reyrolle 7SR45 Argus Device Manual page 54

Hide thumbs Also See for Reyrolle 7SR45 Argus:
Table of Contents

Advertisement

Functions
3.5 Time-Delayed Derived Earth Fault Protection (51N)
The following characteristic curves are supported by 51N-n:
DTL
IEC-NI
IEC-VI
IEC-EI
IEC-LTI
ANSI-MI
ANSI-VI
ANSI-EI
Operating time for IEC
Operating time for IEEE/ANSI
Reset time for IEC/IEEE/ANSI
Table 3-2
Curve Type
IEC-NI
IEC-VI
IEC-EI
IEC-LTI
IEEE/ANSI-MI
IEEE/ANSI-VI
IEEE/ANSI-EI
where,
I - Fault-current Magnitude
I
- Pickup setting
S
T
- Time multiplier
m
Application and Settings Notes
Gn 51N-n Element
Default setting: Disabled
This setting is used to allow the element to be switched on and off if it is not required. A separate setting is
provided for each element. These settings can be used to select the number of elements required.
Parameter State
Disabled
Enabled
54
Constants for Operating-Curve and Reset-Curve Characteristics
K
α
0.14
0.02
13.5
1.0
80
2.0
120
1.0
Description
The element is inactive.
The element is active.
Operating Curve
P
A
0.02
0.0515
2.0
19.61
2.0
28.2
Reset Curve
B
R
n
9.7
2
43.2
2
58.2
2
80
2
0.114
4.85
2
0.491
21.6
2
0.1217
29.1
2
Reyrolle, 7SR45, Device Manual
C53000-G7040-C101-2, Edition 09.2020

Advertisement

Table of Contents
loading

Table of Contents