Functions
3.6 Instantaneous Measured Earth Fault Protection (50G)
Gn 50G-n Setting
Gn 50G-n Delay
Gn 50G-n Inrush
Action
Information List
Input/Output Matrix User Logic
Inhibit 50G-n
50G-n
60
0.2 ⋅ I
to 20.0 ⋅ I
rated
rated
Δ 0.1 ⋅ I
rated
0 s to < 20 s
Δ 0.01 s
≥ 20 s to < 100 s
Δ 0.1 s
≥ 100 s to 600 s
Δ 1 s
Off
Inhibit
Type
Inhibit 50G-n
Input
50G-n
Output
1.0 ⋅ I
rated
0 s
Off
IEC 103
Y
C53000-G7040-C101-2, Edition 09.2020
Modbus RTU
Y