1. Important Health & Safety Information ..................3 1.1 Document Conventions....................4 1.2 Health and Safety Information..................6 1.3 Operating Limits for Standard Dutypoint Systems Pumpsets ......... 9 2. System Information, Installation and Commissioning..............10 2.1 Booster Set Components ....................11 2.2 Control Panel Wiring Diagrams ..................
Electric Shock: Denotes attention to the possibility of life- threatening electric shock if the information is ignored. Warning: Denotes attention to a condition that may result in under- performance or damage to the equipment if the information is ignored. Page 4 VT Booster Set...
Page 5
Note: Denotes attention to an important factor applicable to the action being performed. Page 5 VT Booster Set...
• Normal safety precautions must be taken and appropriate procedures observed to avoid accidents. R efer to DUTYPOINT SYSTEMS for any technical advice or product information. Customer / Contractor Responsibility It is the responsibility of the customer and/or the contractor: •...
Page 7
• CLOSE the isolating valves on the suction and discharge connections of the affected pump(s). • VENT the pump(s) slowly and cautiously – Refer to the relevant section of this manual. • DRAIN the pump(s). High Voltages Especially applicable when Variable Speed Controllers (Inverters) are fitted. Page 7 VT Booster Set...
Page 8
• High voltage tests of the inverter or the motor may damage the electronic components. Bridge before the incoming/outgoing terminals L-L2-L3 and U-V-W. • To avoid incorrect metering by capacitors incorporated in the electronic circuits, isolate the motor from the inverter drive head. Page 8 VT Booster Set...
1.3 Operating Limits for Standard Dutypoint Systems Pumpsets Table showing standard operating limits which apply to cold water booster sets. Table showing standard operating limits Type of pumped liquids Water with no gas or aggressive substances Maximum pumped liquids +35°C domestic uses. (EN 60335-2-41). 40°C for other purposes...
In practice, a system can almost invariably be made to perform more efficiently if further re- commissioning is carried out on site. Please note that engineer visits by Dutypoint are priced at one visit to commission one pump set. If there are multiple units on a site, special terms can be negotiated. To arrange a commissioning visit, please call the Technical Service Help line 01452 300590.
Page 19
If the max. pressure generated by the pump in a system is 6 bar. This will require a pre- charge pressure of 6 x 90% = 5.4 bar. Page 18 VT Booster Set...
Page 20
7. Switch off, re-close the discharge valve and repeat steps 3 to 6 several times to ensure that all air is released from the pump body and local pipework. 8. The above procedure should be carried out individually for each pump in the Pumpset. Page 19 VT Booster Set...
Page 21
The advised procedure should then be carried out individually for each pump in the pumpset. 4. Programming the Controller Dutypoint Systems fit a design of Inverter/Controller that is most suitable for the design duty of the Pumpset. Section 3 of this manual details the type of controller used in the various models, and manufacturer’s information for them is detailed in the Appendices to this manual.
Page 22
Note No manual operation or attendance is required other than for routine servicing and maintenance checks. Other than for maintenance purposes, the supply to the Controller(s) and the Pump motor(s) should never be switched off Page 21 VT Booster Set...
3.1 Routine User Maintenance Dutypoint Pumpsets have been designed to keep major maintenance requirements to a minimum. Planned maintenance of the pumps and other principal components should therefore be undertaken at the intervals recommended in the manuals referenced below. It is essential that a full test following the Pre-Commissioning procedure on page 42 is carried out on an annual basis.
Page 25
Please refer to the manufacturer's document. Detailed Controller Maintenance Please refer to the appropriate manufacturer's document. Detailed Accessory Maintenance If you have purchased additional accessories for your system, please refer to the appropriate manufacture’s document supplied. Page 24 VT Booster Set...
3.2 Troubleshooting The information in this section is common to all Dutypoint centrifugal pumps. For more detailed troubleshooting information that is specific to the type and model of pump and controller used in this product, please refer to the manufacturer's literature.
Page 27
If the pump has a “Hand Control” option on Switching to “Auto” should restore normal control. it’s control panel. If normal control is not returned an immediate service visit is required. Pump has no “Hand Control” option. An immediate service visit is required. Page 26 VT Booster Set...
Page 28
Overload trip setting Check and (if necessary) reset the overload trip value too low for rated duty For pump and controller manufacturer's information refer to the relevant manual. Page 27 VT Booster Set...
This Controller O&M covers models in the following range: VT2/3/4 - 0511 > 1022 Ap 1.3 Grundfos MGE 71/MGE 80/MGE 90/MGE 132 Controller O&M (More than 2.2kW) This Controller O&M covers models in the following range: VT2/3/4 - 1030 > 2075 Page 28 VT Booster Set...
GRUNDFOS INSTRUCTIONS Ap 1.1 Grundfos CR/CRI/CRN Pump O&M CR, CRI, CRN Installation and operating instructions Page 29...
Page 31
Declaration of conformity GB: EC declaration of conformity We, Grundfos, declare under our sole responsibility that the products CR, CRI and CRN, to which this declaration relates, are in conformity with these Council directives on the approximation of the laws of the EC member states: —...
Page 32
English (GB) Installation and operating instructions Original installation and operating instructions. 1. Symbols used in this document CONTENTS Warning Page If these safety instructions are not observed, it may result in personal injury. Symbols used in this document Handling Warning Type designation If these instructions are not observed, it may lead Type key for CR, CRI, CRN 1s, 1, 3, 5, 10, 15 and 20...
Page 33
3. Type designation 5. Technical data 3.1 Type key for CR, CRI, CRN 1s, 1, 3, 5, 10, 15 and 20 5.1 Ambient temperature and altitude Example CR 3- 10 X- X- X- X- XXXX Maximum Maximum Motor Motor altitude Type range: CR, CRI, CRN Motor ambient...
Page 34
5.2 Liquid temperature 5.4 Minimum inlet pressure The table on page states the relationship between liquid temperature range and maximum permissible operating pressure. The maximum permissible operating pressure Note and liquid temperature ranges apply to the pump only. 5.3 Maximum permissible operating pressure and liquid temperature for the shaft seal The diagram below applies to clean water and Note...
Page 35
5.5 Maximum inlet pressure 6. Installation The table on page states the maximum permissible inlet The pump must be secured to a horizontal, plane and solid pressure. However, the actual inlet pressure + maximum pump foundation by bolts through the holes in the base plate. pressure (at no flow) must always be lower than the values stated When installing the pump, follow the procedure below in order to in fig.
Page 36
6.1 Foundation The foundation/installation must be carried out in accordance with the following instructions. Note Non-compliance may result in functional faults which will damage the pump components. Grundfos recommends to install the pump on a concrete foundation which is heavy enough to provide permanent and rigid support to the entire pump.
Page 37
6.3 Outdoor installation 6.6 Flange forces and torques When installed outdoors, it is recommended to provide the motor If not all loads reach the maximum permissible value stated in the with a rain cover. We also recommend to open one of the drain tables below, one of these value may exceed the normal limit.
Page 38
7. Electrical connection 7.2 Three-phase connection The electrical connection should be carried out by an authorised Mains supply [V] electrician in accordance with local regulations. Delta connection Star connection Warning 220-240 380-415 Before removing the terminal box cover and 50 Hz before removing/dismantling the pump, make 380-415 660-690...
Page 39
7.3 Single-phase connection 7.4 Terminal box position The terminal box can be turned to four positions, in 90 ° steps. Mains supply [V] Follow this procedure: 1. If necessary, remove the coupling guards. Do not remove the "Low voltage" "High voltage" coupling.
Page 40
8.1 Shaft seal run-in 10. Frost protection The seal faces are lubricated by the pumped liquid, meaning that Pumps which are not being used during periods of frost should be there may be a certain amount of leakage from the shaft seal. drained to avoid damage.
Page 41
12. Fault finding Warning Before removing the terminal box cover and before removing/dismantling the pump, make sure that the power supply has been switched off and that it cannot be accidentally switched on. Fault Cause Remedy 1. Motor does not run a) Supply failure.
Page 44
Fig. A Maximum permissible operating pressure / liquid temperature range Oval PJE - CLAMP - CA - UNION DIN - FGJ Operating Liquid temperature Operating Liquid temperature pressure range pressure range CR, CRI, CRN 1s 16 bar -20 °C to +120 °C 25 bar -20 °C to +120 °C CR, CRI, CRN 1...
Page 45
Fig. B Maximum inlet pressure for CR, CRI and CRN 50 Hz 60 Hz CR, CRI, CRN 1s CR, CRI, CRN 1s-2 → CR, CRI, CRN 1s-36 CR, CRI, CRN 1s-2 → CR, CRI, CRN 1s-27 10 bar 10 bar CR, CRI, CRN 1 →...
Page 52
Designation Pos. Adapter flange Motor stool Pump head Chamber, top Chamber without neck ring Chamber complete Chamber with bearing ring Chamber complete Base Stop pin Guide plate for base Bearing ring Coupling guard Screw Coupling complete Screw Shaft pin Air vent screw Pipe plug Plug Plug...
Page 58
Quickguide Start-up Close the isolating valve on the discharge side of the pump and Remove the priming plug from the pump head and slowly fill the open the isolating valve on the suction side. pump with liquid. Replace the priming plug and tighten securely. See the correct direction of rotation of the pump on the motor fan Start the pump and check the direction of rotation.
Ap 1.2 Grundfos CRE/CRIE, CRNE/SPKE/MTRE/ CME Controller O&M (Up to 2.2kW) This Controller O&M covers models in the following range: VT2/3/4 - 0511 > 1022 CRE, CRIE, CRNE, SPKE, MTRE, CME Installation and operating instructions, supplement Functional descriptions GRUNDFOS INSTRUCTIONS Installation and operating instructions http://net.grundfos.com/qr/i/98358864 Page 30...
Page 60
English (GB) Installation and operating instructions Original installation and operating instructions. Identification of control panel Changing the position of the control panel CONTENTS Factory settings Page Disposal Symbols used in this document General information Warning User interfaces Prior to installation, read these installation and operating instructions.
Page 61
4. Standard control panel The pumps are fitted with this control panel as standard. Fig. 2 Setpoint set to 3 bar, constant pressure control 4.1.2 Pump in constant-curve control mode Stop In constant-curve control mode, the pump performance will lie between the maximum and minimum curve of the pump.
Page 62
Setting to minimum curve: 5. Advanced control panel • Press continuously to change over to the minimum curve The pumps can be fitted with the advanced control panel as an of the pump (bottom light field flashes). When the bottom light option.
Page 63
5.1 Home display Pos. Symbol Description Makes the pump ready for operation/starts and stops the pump. Start: If you press the button when the pump is Status Settings Assist stopped, the pump will only start if no other Setpoint Control mode functions with higher priority have been enabled.
Page 64
5.3 Menu overview for advanced control panel 5.3.1 Home CRE, CRIE, Multipump Home CRNE, SPKE, system MTRE ● ● ● 5.3.2 Status CRE, CRIE, Multipump Status CRNE, SPKE, system MTRE Operating status ● ● ● Operating mode, from ● ● ●...
Page 66
Continued from page 7. CRE, CRIE, Multipump Settings CRNE, SPKE, Section Page system MTRE General settings ● ● ● Language ● ● ● 7.26 Language Set date and time ● ● ● 7.27 Date and time (Set date and time) Units ●...
Page 67
6. Grundfos GO 6.1 Communication When Grundfos GO initiates communication with the pump, the The pump is designed for wireless radio or infrared indicator light in the middle of Grundfos Eye will flash green. See communication with Grundfos GO. section 10.
Page 68
6.2 Menu overview for Grundfos GO CRE, CRIE, Multipump Dashboard CRNE, SPKE, system MTRE ● ● ● CRE, CRIE, Multipump Status CRNE, SPKE, system MTRE System mode ● Resulting setpoint ● ● Resulting system setpoint ● Actual controlled value ● ●...
Page 69
Continued from page 10. CRE, CRIE, Multipump Settings CRNE, SPKE, Section Page system MTRE Analog input 1 ● ● Analog input 2 ● ● 7.5 Analog inputs Analog input 3 ● ● Pt100/1000 input 1 ● ● 7.6 Pt100/1000 inputs Pt100/1000 input 2 ●...
Page 70
7. Description of functions 7.4 Control mode 7.1 Setpoint Pump variant Control mode ● Pump variant Setpoint CRE, CRIE, CRNE, SPKE, MTRE ● ● Possible control modes: CRE, CRIE, CRNE, SPKE, MTRE ● • Constant pressure (Const. pressure) You can set the setpoint for all control modes when you have •...
Page 71
7.4.2 Constant temperature 7.4.3 Constant differential pressure Pump variant Constant temperature Constant differential Pump variant pressure ● ● CRE, CRIE, CRNE, SPKE, MTRE ● CRE, CRIE, CRNE, SPKE, MTRE ● This control mode ensures a constant temperature. Constant temperature is a comfort control mode that can be used in The pump maintains a constant differential pressure, domestic hot-water systems to control the flow to maintain a fixed independently of the flow in the system.
Page 72
7.4.4 Constant differential temperature 7.4.5 Constant flow rate Constant differential Pump variant Constant flow rate Pump variant temperature ● ● CRE, CRIE, CRNE, SPKE, MTRE ● CRE, CRIE, CRNE, SPKE, MTRE ● The pump maintains a constant flow in the system, independently The pump maintains a constant differential temperature in the of the head.
Page 73
7.4.6 Constant level 7.4.7 Constant other value Pump variant Constant level Pump variant Constant other value ● ● CRE, CRIE, CRNE, SPKE, MTRE ● CRE, CRIE, CRNE, SPKE, MTRE ● The pump maintains a constant level, independently of the flow Any other value is kept constant.
Page 74
7.5 Analog inputs Sensor function/measured parameter Pos. Available inputs depending on the functional module fitted in the Inlet pressure pump: Diff. press., inlet FM 200* FM 300* Function (terminal) Discharge press. (standard) (advanced) Diff. press.,outlet Analog input 1, setup (4) ●...
Page 75
7.6 Pt100/1000 inputs 7.7 Digital inputs Available inputs depending on the functional module fitted in the Pump variant Digital inputs pump: ● FM 200* FM 300* Function (terminal) CRE, CRIE, CRNE, SPKE, MTRE ● (standard) (advanced) Available inputs depending on the functional module fitted in the Pt100/1000 input 1, setup ●...
Page 76
7.8 Digital inputs/outputs Possible functions, digital input/output 4 Function if output Pump variant Digital inputs/outputs Function if input (See details in section (See details in section ● 7.9 Signal relays 1 and 2 7.7 Digital inputs) CRE, CRIE, CRNE, SPKE, MTRE ●...
Page 77
7.10 Analog output • Motor load Motor load Pump variant Analog output Signal range ● [V, mA] CRE, CRIE, CRNE, SPKE, MTRE ● 0-10 V 10 V Whether the analog output is available or not, depends on the 0-20 mA 0 mA 10 mA 20 mA...
Page 78
7.11 Controller ( Controller settings Constant differential temperature Controller Pump variant (Controller settings) ● CRE, CRIE, CRNE, SPKE, MTRE ● The pumps have a factory default setting of gain (K ) and integral time (T -0.5 10 + 5L2 However, if the factory setting is not the optimum setting, you can change the gain and the integral time: •...
Page 79
7.12 Operating range Example with constant curve with linear influence Actual setpoint = actual input signal x (setpoint - user set min. speed) + user set min. speed. Pump variant Operating range At a "user set min. speed." of 25 %, and a setpoint of 85 % and an ●...
Page 80
• Linear with Stop and Inverse with Min. • Inverse with Stop and Inverse with Min. – Inverse with Stop – Inverse with Stop In the input signal range from 20 to 100 %, the setpoint is In the input signal range from 0 to 80 %, the setpoint is influenced linearly.
Page 81
• Influence table with Stop at Min. Factory setting The setpoint is influenced by a curve made out of two to eight See section 16. Factory settings. points. There will be a straight line between the points and a 7.14 Predefined setpoints horizontal line before the first point and after the last point.
Page 82
7.15 Limit-exceeded function Example: The "Limit-exceeded function" is to monitor the discharge Pump variant Limit-exceeded function pressure from a CRE pump. If the pressure is below 5 bar for more than 5 seconds, a warning must be given. If the discharge ●...
Page 83
7.17 Stop function (Low-flow stop function) Stop function Pump variant (Low-flow stop function) ● CRE, CRIE, CRNE, SPKE, MTRE ● Stop pressure You can set the low-flow stop function to these values: • Not active Start pressure • Energy-optimal mode •...
Page 84
Operating conditions for the low-flow stop function 7.18 Pipe filling function You can only use the stop function if the system incorporates a pressure sensor, a non-return valve and a diaphragm tank. Pump variant Pipe filling function ● Always install the non-return valve before the Caution CRE, CRIE, CRNE, SPKE, MTRE ●...
Page 85
7.19 Pulse flowmeter (Pulse flowmeter setup) 7.21 Standstill heating Pulse flowmeter Pump variant Standstill heating Pump variant (Pulse flowmeter setup) ● ● CRE, CRIE, CRNE, SPKE, MTRE ● CRE, CRIE, CRNE, SPKE, MTRE ● You can use the function to avoid condensation in humid You can connect an external pulse flowmeter to one of the digital environments.
Page 86
7.23 Service 7.27 Date and time (Set date and time) Time to next service (Motor bearing service) Date and time This display shows when to replace the motor bearings. The Pump variant (Set date and time) controller monitors the operating pattern of the motor and calculates the period between bearing replacements.
Page 87
7.29 Buttons on product (Enable/disable settings) 7.33 Store settings (Store actual settings) Buttons on product Store settings Pump variant Pump variant (Enable/disable settings) (Store actual settings) ● ● CRE, CRIE, CRNE, SPKE, MTRE ● CRE, CRIE, CRNE, SPKE, MTRE ● In this display, you can disable the possibility of making settings Grundfos GO for protective reasons.
Page 88
7.36 Connection code • Setting of pump – Go to Home Pump variant Connection code – Run with Constant curve/Run with Constant pressure. (See section 7.4 Control mode. ● – Go to "Assisted pump setup". CRE, CRIE, CRNE, SPKE, MTRE ●...
Page 89
Advanced control panel 7.44 Multi-pump setup (Setup of multi-pump system) 1. Open the "Assist" menu. Multi-pump setup 2. Select "Assisted pump setup". Pump variant (Setup of multi-pump 3. Select control mode "Const. pressure". system) 4. Select which analog input to be used as sensor input. ●...
Page 90
7.44.3 Setting up a multipump system Grundfos GO and wired pump connection 1. Connect the two pumps with each other with a 3-core You can setup a multipump system in the following ways: screened cable between the GENIbus terminals A, Y, B. •...
Page 91
Advanced control panel and wireless pump connection Disabling a multipump system via Grundfos GO 1. Power on both pumps. 1. Select the "Assist" menu. 2. On both pumps, set up the needed analog and digital inputs 2. Select "Multi-pump setup". according to the connected equipment and the required 3.
Page 92
8. Bus signal The pump enables serial communication via an RS-485 input. The communication is carried out according to the Grundfos GENIbus protocol and enables connection to other pumps as well as a building management system or another external control system.
Page 93
10. Grundfos Eye The operating condition of the pump is indicated by Grundfos Eye on the control panel. See fig. 43, pos. A. Fig. 43 Grundfos Eye Grundfos Eye Indication Description Power off. No lights on. Pump not running. Two opposite green indicator lights rotating Power on.
Page 94
11. Signal relays The pump has two outputs for potential-free signals via two internal relays. You can set the signal outputs to "Operation", "Pump running", "Ready", "Alarm" and "Warning". The functions of the two signal relays appear from the table below: Contact position for signal relays when activated Operating...
Page 95
12. Installation of communication interface 4. Remove the securing screw (fig. 47, pos. A). module (CIM) Always use an antistatic service kit when handling electronic components. This will prevent static electricity from damaging Caution components. When unprotected, place the component on the antistatic cloth.
Page 96
9. Route the wires for the CIM module, see the example in fig. Fig. 50 Wire routing (example) 10. Fit the CIM cover. 11. If the CIM module is supplied with an FCC label, then place this on the terminal box. See fig. 51. Fig.
Page 97
13. Identification of functional module 14. Identification of control panel You can identify the fitted module in one of the following ways: You can identify the fitted module in one of the following ways: Grundfos GO Grundfos GO You can identify the functional module in the "Fitted modules" You can identify the control panel in the "Fitted modules"...
Page 98
15. Changing the position of the control panel 4. Turn the plastic cover 180 °. You can turn the control panel 180 °. Follow the instructions Note Do not twist the cable more than 90 °. below. 1. Loosen the four screws (TX25) holding the terminal box cover. Fig.
Page 99
16. Factory settings ● Function is enabled. ❍ Function is disabled. Function is not available. CRE, CRIE, CRNE, SPKE, MTRE Function Settings With factory mounted Without factory description sensor mounted sensor Setpoint 67 % of sensor range 67 % of sensor range 67 % of sensor range Page Operating mode...
Ap1.3 Grundfos MGE 71/MGE 80/MGE 90/MGE 132 Controller O&M (More than 2.2kW) This Controller O&M covers models in the following range: VT2/3/4 - 1030 --> 2075 MGE 71, MGE 80 MGE 90 - MGE 132 Advanced Installation and operating instructions GRUNDFOS INSTRUCTIONS Page 31...
Page 101
English (GB) Installation and operating instructions Original installation and operating instructions. 18.3 Inputs/output Other technical data CONTENTS 19.1 Sound pressure level Disposal Page Symbols used in this document Warning General description Prior to installation, read these installation and Identification operating instructions. Installation and operation Type key must comply with local regulations and accepted codes of good practice.
3. Identification 4.3 Outdoor installation When installed outdoors, the motor must be provided with a The motor is identified by means of the nameplate on the terminal suitable cover to avoid condensation on the electronic box. components, fig. 2. Fig. 1 Nameplate Fig.
5. Electrical connection - single-phase motors 5.6 Supply voltage • 1 x 230-240 V ± 10 %, 50/60 Hz, PE. The user or the installer is responsible for the • 1 x 200-220 V ± 10 %, 50/60 Hz, PE. installation of the correct earthing and protection The supply voltage and frequency are marked on the motor Caution...
5.8 Other connections 6. Electrical connection - three-phase motors The connection terminals of external potential-free contacts for The user or the installer is responsible for the start/stop and digital functions, external setpoint signal, sensor installation of the correct earthing and protection signal, GENIbus and relay signal are shown in fig.
6.3 Additional protection MGE 90 to MGE 132 If the motor is connected to an electric installation where an earth leakage circuit breaker is used as additional protection, this circuit breaker must be of the type: • which is suitable for handling leakage currents and cutting-in with short pulse-shaped leakage.
6.9 Other connections 7. Signal cables The connection terminals of external potential-free contacts for • Use screened cables having a cross-sectional area of min. start/stop and digital functions, external setpoint signal, sensor 0.5 mm and max. 1.5 mm for external on/off switch, digital signal, GENIbus and relay signal are shown in fig.
8. Setting of motor 9.1 Setpoint setting The setpoint of the motor is set by pressing the button The motor incorporates a control panel enabling setting of setpoint, changeover to max. frequency or to min. frequency and The yellow light fields on the control panel will indicate the start/stop of motor.
9.5 Setting to min. frequency Press continuously to change over to the min. frequency (bottom light field flashes). When the bottom light field is on, must be pressed for 3 secs. before the light field starts flashing. To change back, press continuously until the desired setpoint is indicated.
10. Setting by means of R100 During communication, the R100 must be pointed at the control panel. When the R100 communicates with the motor, the red The motor is designed for wireless communication with the indicator light will flash rapidly. Grundfos remote control R100.
10.1 Menu 10.1.2 Setting of operating mode OPERATION When communication between the R100 and the motor has been established, the first display in this menu will appear. 10.1.1 Setpoint setting Select one of the following operating modes: • Stop, • Min.
10.1.4 Fault log 10.2.2 Display of operating mode For both fault types, alarm and warning, the R100 has a log function. Alarm log This display shows the actual operating mode (Stop, Min., Normal (duty) or Max.). Furthermore, it shows where this operating mode was selected (R100, Motor, BUS or External).
10.2.7 Display of motor current 10.3 Menu INPUT/OUTPUT 10.3.1 Selection of control mode Tolerance: ± 5 % • Motor current indicates the actual motor input current from Select one of the following control modes: the frequency converter. • Closed loop, •...
Page 113
10.3.3 Selection of external setpoint signal 10.3.5 Selection of function for digital inputs Motor digital inputs (see also fig. or 11): • Terminals 1 and 9 --> digital input 2. • Terminals 10 and 9 --> digital input 3. • Terminals 11 and 9 -->...
10.4 Menu FUNCTIONS 10.4.5 Allocation of motor number 10.4.1 Selection of function in case of overload A number between 1 and 64 can be allocated to the motor or can be changed. In connection with bus communication, a number Select the function required in case of overload: must be allocated to each motor.
Page 115
Table values: 10.5.2 Setting of ramps The tables show the relationship between the nameplate data for and n and the factory-set values for f and f max. min. max. min. • corresponds to the maximum speed stated on the motor max.
10.5.6 Motor bearing monitoring (only three-phase motors) 11.1 Start/stop input Functional diagram: Start/stop input: Start/stop (terminals 2 and 3) Normal Normal duty The motor bearing monitoring function can be set to these values: • Active • Not active. Stop When the function is set to Active, a counter in the controller will start counting the mileage of the bearings.
12. External setpoint signal 13. Bus signal By connecting an analog signal transmitter to the input for the Note Only if the optional GENIbus terminal is fitted. setpoint signal (terminal 4), it is possible to remote-set the setpoint. The motor enables serial communication via an RS-485 input. The actual external signal (0-10 V, 0-20 mA, 4-20 mA) must be The communication is carried out according to the Grundfos bus selected via the R100, see section...
15. Indicator lights and signal relay The motor has an output for a potential-free signal via an internal relay. The operating condition of the motor is indicated by the green and The signal output can be set to fault, operating or ready indication red indicator lights in the motor terminal box, fig.
16. Megging Signal output Potential-free changeover contact. Megging of an installation incorporating MGE Maximum contact load: 250 VAC, 2 A. Note motors is not allowed, as the built-in electronics Minimum contact load: 5 VDC, 10 mA. may be damaged. Screened cable: 0.5 - 2.5 mm / 28-12 AWG.
Sensor signals 19.1 Sound pressure level • Voltage signal Single-phase motors: 0-10 VDC, R > 0 kΩ (via internal voltage supply). < 70 dB(A). Tolerance: + 0 %/- 3 % at maximum voltage signal. Three-phase motors: Screened cable: 0.5 - 1.5 mm / 28-16 AWG.
Page 121
Appendix Appendix 1. Installation in the USA and Canada Europe - kW 2-pole 4-pole Fuse size Circuit breaker type/model In order to maintain the UL/cURus approval, Note follow these additional installation instructions. 0.55 25 A 25 A / Inverse time The UL approval is according to UL508C.
Page 122
Declaration of conformity GB: EC declaration of conformity DK: EF-overensstemmelseserklæring We, Grundfos, declare under our sole responsibility that the products Vi, Grundfos, erklærer under ansvar at produkterne MGE 71, MGE 80, MGE 71, MGE 80, MGE 90, MGE 100, MGE 112 and MGE 132, to which MGE 90, MGE 100, MGE 112 og MGE 132 som denne erklæring this declaration relates, are in conformity with these Council directives on omhandler, er i overensstemmelse med disse af Rådets direktiver om...
Page 123
Declaration of conformity RU Электродвигатели серии MG, MGE сертифицированы на соответствие требованиям Технического регламента Таможенного союза ТР ТС 004/2011 «О безопасности низковольтного оборудования»; ТР ТС 020/2011 «Электромагнитная совместимость технических средств». Сертификат соответствия: № ТС RU C-DK.АИ30.В.00417, срок действия до 02.12.2018г. Истра, 1 апреля...
Need help?
Do you have a question about the VT Booster Set and is the answer not in the manual?
Questions and answers