Instruction Manual
Dust Ignition proof type LED Lighting Fittings
Thank you very much for purchasing our LED lighting fittings.
Please read this instruction manual to use the product properly.
After installing the product, be sure to hand this manual over to the user of the product.
Prior to use
Performance
1)
The electrical characteristic data is given below (the figure in angle brackets < > in the Installation Type column is a sign placed at the end of
each model code to represent the type of installation.)
Model
Installation Type
Direct mount
LKAB07034
Pipe pendant
Bracket
LKAB07035
Stanchion
Special direct mount
LKAB07031
Horizontal pole mount
LKAB07032
Lamp house replacemen
Direct mount
LKAB07024
Pipe pendant
Bracket
LKAB07025
Stanchion
Special direct mount
LKAB07021
Horizontal pole mount
LKAB07022
Lamp house replacemen
2) Usable in hazardous areas where there may be deflagrative or flammable dust.
Names of the Components and Installation Method
- Installation work should be done properly by a qualified electrician in accordance with the related laws and the instruction manual.
- For safety, Installation work should be done by at least two workers.
■ Direct Mount Type, Pipe Pendant Type, Bracket Type (Fig. 1: Example LKAB070341)
Terminal box
Suspension hook
Pipe
3-Locking screws
Fig. 1
1) Prior to installing the fitting, check if the product is as per your order.
2) Check for a loose or damaged part due to an accident in transit, etc.
Input Voltage
(Frequency)
<1>
<2>
<6>
<1,1H>
<1>
<4>
100-242V AC
(50/60Hz)
<1>
<2>
<6>
<1,1H>
<1>
<4>
4-φ holes for M6 olts
Suspension hook hole
Cover gasket
Terminal box cover
4-Cross recessed
hexagon bolts
Lamp house
Input
Power
Current
Consumption
0.26-0.12A
25.5-26W
0.19-0.08A
18-18.5W
Fix the terminal box on a horizontal mounting surface securely with M6
bolts or equivalent bolts.
NB: For the bracket type, fix it on a vertical mounting surface securely.
Screw the pipe into the lamp house.
Screw the terminal box cover into the pipe.
Lift the lamp house and hook the suspension hook onto the suspension
hook hole of the terminal box.
After connection of the electric wires (white and black: power wires,
green: grounding wire), remove the suspension hook and put it in the
terminal box cover.
Fasten the terminal box and its cover with four cross recessed hexagon
bolts.
After adjusting the positions of the lamp house and terminal box,
tighten the three locking screws.
NB1:
The pipe, locking screws and cross recessed hexagon blots should be
tightened securely. Otherwise, the lamp house might fall.
NB2: Caulk the threaded connections.
NB3:
For the bracket type, the lamp house may be installed within an
angle range of 0° (down) to 45° (oblique). For the direct mount and
Pipe pendant type, The lamp house may be installed within an angle
range of 0° (down).
For the direct mount and Pipe pendant type, The lamp house may
be installed within an angle range of 0° (down).
- -
11E0200002A11
To be conserved
LKAB
Type of
IP
protection
rating
SDP-13
IP65
Need help?
Do you have a question about the LKAB07034 and is the answer not in the manual?