Download Print this page

Seiwa WLZAA14021 Instruction Manual

Explosion proof/ dust ignition proof type led lighting

Advertisement

Quick Links

EXPLOSION PROOF/ DUST IGNITION PROOF TYPE LED LIGHTING
Thank you very much for purchasing our EXPLOSION PROOF / DUST IGNITION PROOF TYPE LED
The type of protection of this product is as follows:
Ex d ⅡC T6 Gb
Ex tD A21 IP66 T85℃
GB 3836.1-2010
GB 3836.2-2010
GB 12476.1-2013
GB 12476.5-2013
Usable in hazardous areas of zone 1 , zone 2 , zone 21 and zone 22 where there is explosive atmospheres.
The product should be of the flameproof type suitable for each hazardous area.
Use of an unsuitable product might cause an explosion or fire.
The product of 14W*2 should be used within an ambient temperature range of -20ºC to +55ºC.
The product of 15.5W*2should be used within an ambient temperature range of -20ºC to +40ºC.
If the ambient temperature is out of the range, an explosion or fire might result.
For electrical connection, be sure to connect the wires in the terminal box securely using crimp-type
terminals, etc. and conduct insulation treatment. An inadequate connection or inadequate insulation might
cause a contact failure, leading to an explosion, fire or electric shock.
The product should be mounted properly according to the instruction manual, on a surface robust enough to
support its weight.
Improper installation might cause fall of the product, an electric shock or injury.
INSTRUCTION MANUAL
WARNING
1

Advertisement

loading
Need help?

Need help?

Do you have a question about the WLZAA14021 and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Seiwa WLZAA14021

  • Page 1 INSTRUCTION MANUAL EXPLOSION PROOF/ DUST IGNITION PROOF TYPE LED LIGHTING Thank you very much for purchasing our EXPLOSION PROOF / DUST IGNITION PROOF TYPE LED WARNING The type of protection of this product is as follows: Ex d ⅡC T6 Gb Ex tD A21 IP66 T85℃...
  • Page 2 WARNING When leading the power cable into the product, be sure to follow the technical standards for electrical equipment and the guide for the explosion protection of factory electrical equipment. Inadequate cable connection or poor waterproofing might cause an explosion, fire or electric shock. In grounding work, follow the technical standards for electrical equipment and the guide for the explosion protection of factory electrical equipment.
  • Page 3: Assembly And Installation

    (2) Check for a loose or damaged part due to an accident in transit, etc. ■Performance of the product (1) The electrical characteristics of the product are as follows: Input Voltage Frequency Input Current Model LED Wattage Input Wattage (AC) (AC) WLZAA14021 14W×2 220-240V 50/60Hz 0.13-0.14 A 27-29 W WLZAA15021 14.7W×2 220-240V 50/60Hz 0.13-0.14A...
  • Page 4 (2) After loosen the set screw, open the cap in using accessory special tool. (3) Remove three connecters. Install power wires and earthing wire and set connecters to original Connecters position. No gap (4) According to the left figure, it should be grounded the external ground reliably by using attached crimp terminal.
  • Page 5: Maintenance

    Maintenance (1) In cleaning the fitting, gently wipe with water or mild detergent. Don’t use thinner, benzene or alkaline detergent. Such chemicals might cause discoloration or deterioration in quality and strength, resulting in a damage. (2) Prior to maintenance, be sure to turn off the power. (3) Conduct inspection properly referring to the table below.
  • Page 6 19. Don’t move the product only holding the guard, please move it carefuuly. CONTACT SEIWA ELECTRIC MFG. CO., LTD. ■For further information on the product, contact our offices below (let us know the model name indicated on the nameplate).