Specifications; Technical Data For The Swimming Pool Heat Pump Unit - Hayward ENERGYLINE PRO INVERTER Installation Instructions Manual

Swimming pool heat pump unit
Table of Contents

Advertisement

2. SPECIFICATIONS

2.1 Technical data for the swimming pool heat pump unit

Models
Rated heating capacity
(a)
Electrical power consumption
COP
(a)
Power supply
Phase
Frequency
Rated service current
(a)
Maximum service current (CMS)
aM type fuse calibre
Curve D circuit breaker
Starting current
Hydraulic connection
Nominal water flow
(a)
Water pressure drop (max)
Compressor
Type
Quantity
Refrigerant
Weight of refrigerent
teqCO
2
Leak control frequency
Fan
Diameter
Quantity
Motor
Quantity
Rotation speed
Sound pressure level (at 1 meter)
Sound pressure level (at 10 meters)
Unit net dimensions (L/l/h)
Net weight per unit
(a) The rated heating capacities are based on Test standard NF-EN 14511, used in reference framework NF-414.
Dry air 15°C - Relative humidity 71% - Incoming water temperature 26°C.
4
ENERGYLINE PRO
INVERTER
kW
kW
(a)
/
V
/
Hz
A
A
aM
D
A
mm
m
/h
3
kPa
/
/
/
/
kg
/
/
/
mm
/
/
/
Tr/min
dB(A)
dB(A)
mm
kg
ENPI7M
ENPI9M
7,05
9,20
1,33
1,81
5,30
5,08
230V
230V
1N
1N
50 Hz
50 Hz
5,69
7,8
15,5
21
16
25
16
25
< CMS
< CMS
3,20
4,00
4,60
7,00
Rotary
Inverter
R410A
1,10
1,30
2,30
2,71
Not compulsory but recommended
Axial
1
1
Inverter
1
1
500...750
500...900
44-53
45-56
27-36
28-39
1117 / 485 / 868
77
82
ENPI11M
ENPI13T
11,40
13,40
2,18
2,60
5,23
5,15
230V
400V
1N
3N
50 Hz
50 Hz
9,32
4,47
25,9
11,4
32
16
32
16
< CMS
< CMS
50
4,70
5,70
11,60
5,10
1
1,80
2,10
3,76
4,38
500
2
2
2
2
400...800
400...850
46-57
48-58
29-40
31-41
1115 / 485 / 1275
110
113

Advertisement