Article number
LLDP
Encryption
Web server
HTTP
HTTPS
OPC UA
Runtime license required
OPC UA Client
Application authentication
Security policies
User authentication
Number of connections, max.
Number of nodes of the client interfac-
es, max.
Number of elements for one call of
OPC_UA_NodeGetHandleList/OPC_UA_R
eadList/OPC_UA_WriteList, max.
Number of elements for one call of
OPC_UA_NameSpaceGetIndexList, max.
Number of elements for one call of
OPC_UA_MethodGetHandleList, max.
Number of simultaneous calls of the cli-
ent instructions per connection (except
OPC_UA_ReadList,OPC_UA_WriteList,OP
C_UA_MethodCall), max.
Number of simultaneous calls of the cli-
ent instructions
OPC_UA_ReadList,OPC_UA_WriteList
and OPC_UA_MethodCall, max.
Number of registerable nodes, max.
Number of registerable method calls of
OPC_UA_MethodCall, max.
Number of inputs/outputs when calling
OPC_UA_MethodCall, max.
OPC UA Server
Application authentication
Security policies
User authentication
GDS support (certificate management)
CPU 1511-1 PN (6ES7511-1AK02-0AB0)
Equipment Manual, 05/2021, A5E40869673-AB
6ES7511-1AK02-0AB0
Yes
Yes; Optional
Yes; Standard and user pages
Yes; Standard and user pages
Yes; "Small" license required
Yes
Yes
Available security policies: None, Basic128Rsa15,
Basic256Rsa15, Basic256Sha256
"anonymous" or by user name & password
4
1 000
300
20
100
1
5
5 000
100
20
Yes; Data access (read, write, subscribe), method
call, custom address space
Yes
Available security policies: None, Basic128Rsa15,
Basic256Rsa15, Basic256Sha256
"anonymous" or by user name & password
Yes
Technical specifications
45