5.9 PRESSURE RELIEF OPTION
The optional pressure relief valve on the single inlet portable base can be adjusted to open between 90 and 300 psi. The pressure
relief valve, TFT part A1820, is set at the factory to open at 150 psi. To change the relief pressure refer to the label on the bottom side
of the pressure relief valve. A pressure relief valve can be added to the single inlet portable base by removing the cover on the side
of the base. For additional information call 800-348-2686.
5.10 PRESSURE RELIEF VALVE SETTING
To set the relief valve pressure turn the adjusting screw on the relief valve housing until the surface of the screw is even with the
desired pressure. Do not cap or plug discharge opening.
6.0 PORTABLE BASE STORAGE
The portable base may be stored in a compartment, on the optional storage bracket, TFT part number XF-B. This bracket is NOT
designed to withstand the reaction forces of an operating monitor stream. It is to be used for storage and transportation only. The
storage bracket may be mounted on a horizontal surface, horizontally or vertically on a vertical surface, or on the underside of a
horizontal surface such as the top of a compartment. A strap helps hold the base on the bracket. Mounting instructions are supplied
with the bracket.
©Copyright Task Force Tips LLC 1999-2018
XF-B
STORAGE
BRACKET
1
Adjusting
Screw
Relief Valve
Discharge
Opening
2
3
14