Table 36.
Low Output Units Standard Vertical Unit with All Air Ports Open** (continued)
Water
Temp.
Drop
Output MBH
Model No.
°F (°C)
(kW)
20°
310.5
500L
(11.1°)
(91.0)
30°
281.7
(16.7°)
(82.5)
10°
394.4
(5.6°)
(115.6)
20°
377.0
600L
(11.1°)
(110.5)
30°
342.2
(16.7°)
(100.3)
20°
453.7
720L
(11.1°)
(132.9)
30°
411.7
(16.7°)
(120.6)
**Performance based on 200° EWT, 20° T.D., 60° E.A.T. Performance at 10° & 30° T.D. is also shown. For capacities at other conditions, use the correction multipliers in the
tables on page 17.
*Speed controller option is required for reduced ratings.
Table 37.
HOT WATER CALCULATIONS AND CORRECTION FACTOR P STYLE
I. CAPACITY @ 20° TD:
A. For 200° EWT, 60° EAT
B. For EWT and/or EAT above or below
Standard
II. CAPACITY AT OTHER TD's
A. For TD's from 5 to 60°F
III. GPM AT OTHER TD's
A. For TD's from 5 to 60°F
IV. PRESSURE LOSS AT OTHER TD's
A.ForTD's from 5 to 60°F
UH-SVX01A-EN
Hot Water Performance Data
Final
Press. Drop
Flow Rate
ft/water
Temp.
G.P.M. (L/s)
m/water
°F (°C) Motor H.P. (kW) R.P.M.
32.00
4.23
90.5°
(2.019)
(1.290)
(32.5)
19.35
1.67
87.7°
(1.221)
(.509)
(30.9)
54.19
6.83
95.3°
(3.418)
(2.083)
(35.2)
38.85
3.68
93.7°
(2.451)
(1.122)
(34.3)
23.51
1.45
90.6°
(1.483)
(.442)
(32.6)
46.76
4.11
95.1°
(2.950)
(1.254)
(35.1)
28.28
1.62
91.9°
(1.784)
(.494)
(33.3)
Read output directly from
22,700 BTU/HR (Ref., Std. 042, p. 12).
Multiply output from
Table 35
Table
38.
Multiply output obtained in IA. or IB.
(above) by appropriate factor from
Multiply GPM of unit for 20° TD, from
by appropriate factor from
Multiply P.D. of unit for 20° TD, from
by appropriate factor from
Air.
1-1/2
1160
(1.119)
1-1/2
1160
(1.119)
3
1165
(2.237)
Table 35
&
Table
36,
&
Table 36
by factor from
Table 39
Table 35
&
Table 36
Table 39
Table 35
&
Table 36
Table 39
Nominal
Outlet
CFM
Velocity
3
(m
/s)
FPM (m/s) Sound Rating
9380
1860
IV
(4.377)
(9.449)
10,300
2060
IV
(4.807)
(10.465)
11,900
2380
IV
(5.553)
(12.090)
EXAMPLE:
UNIT SIZE _________________042
Entering Water Temp. _____160°F
Entering Air Temp. ________ 40°F
Water Temperature Drop ____ 10°F
22,700 x .878 = 19,931 BTU/HR.
IA - 22,700 x 1.15 = 26,105 BTU/HR.
-OR-
IB - 19,931 x 1.15 = 22,921 BTU/HR.
2.34 x 2.30 = 5.38 GPM (Applies only
to units with. Std. 200° EWT, 60° EAT.)
For all others calculate using formula -
GPM = BTU/500 x TD
.06 x 5.00 = .30 Ft. H
O
2
53