Maximum Mounting Height in Feet with and without Louver Cone Diffuser
Unit Size
Steam Pressure (PSI)
2
(13.8)
(34.5)
10.5
10.0
(3.2)
(3.0)
042
12.5
12.0
(3.8)
(3.7)
7.5
7.5
(2.3)
(2.3)
042*
9.0
8.5
(2.7)
(2.6)
12.5
12.0
(3.8)
(3.7)
042L
14.5
14.0
(4.4)
(4.3)
9.0
8.5
(2.7)
(2.6)
042L*
10.5
10.0
(3.2)
(3.0)
12.0
11.5
(3.7)
(3.5)
064
14.5
14.0
(4.4)
(4.3)
9.5
9.0
(2.9)
(2.7)
064*
11.5
11.0
(3.5)
(3.4)
15.0
14.5
(4.6)
(4.4)
064L
19.0
18.5
(5.8)
(5.6)
11.5
11.0
(3.5)
(3.4)
064L*
14.0
13.5
(4.3)
(4.1)
15.0
14.5
(4.6)
(4.4)
080
18.5
18.0
(5.6)
(5.5)
11.0
10.5
(3.4)
(3.2)
080*
13.5
13.0
(4.1)
(4.0)
NOTES:
* = Low Speed
L = Low output model with all air ports open
Figures in bold face show maximum mounting height with louver cone diffusers set vertically.
Above table based on 60°F entering air temperature. In providing for the use of diffusers, it must be remembered that adjustment of a LCD to deflect air
toward horizontal immediately lowers the mounting height limit.