Kohler 15RYG Installation Manual page 43

Commercial generator sets
Hide thumbs Also See for 15RYG:
Table of Contents

Advertisement

6.1 Voltage Reconnection
The
reconnection
procedure
reconnections only.
Some 30kW models are now
available factory-configured for 50 Hz. Do not attempt
to change the frequency from 60 Hz to 50 Hz (or vice-
versa) in the field.
The following instructions explain the reconnection of
12-lead generator sets. In all cases, follow the National
Electrical Code (NEC) guidelines.
Reconnect the stator leads of the generator set if a
different output phase or voltage is desired. Refer to the
following procedure and the connection schematics.
Refer to Section 5 for instructions to make adjustments
though the ADC 2100 menus when instructed in the
procedure. Follow all safety precautions at the front of
this manual and in the text while performing this
procedure.
Note: Order voltage reconnection decal 246242 from
an authorized service distributor/dealer and affix
decal to generator set after reconnecting to a
voltage different than the nameplate.
WARNING
Accidental starting.
Can cause severe injury or death.
Disconnect the battery cables before
working
on the
Remove the negative (--) lead first
when disconnecting the battery.
Reconnect the negative (--) lead last
when reconnecting the battery.
TP-6329 8/07
explains
voltage
generator set.
Section 6 Generator Reconnection
Disabling the generator set.
cause severe injury or death.
generator set or connected equipment, disable the generator
set as follows: (1) Move the generator set master switch to the
OFF position. (2) Disconnect the power to the battery charger.
(3) Remove the battery cables, negative (--) lead first.
Reconnect the negative (--) lead last when reconnecting the
battery. Follow these precautions to prevent starting of the
generator set by an automatic transfer switch, remote
start/stop switch, or engine start command from a remote
computer.
Hazardous voltage.
Can cause severe injury or death.
Operate the generator set only when
all guards and electrical enclosures
are in place.
Grounding electrical equipment. Hazardous voltage can
cause severe injury or death. Electrocution is possible
whenever electricity is present. Ensure you comply with all
applicable codes and standards.
generator set, transfer switch, and related equipment and
electrical circuits. Turn off the main circuit breakers of all
power sources before servicing the equipment. Never contact
electrical leads or appliances when standing in water or on wet
ground because these conditions increase the risk of
electrocution.
Short circuits.
Hazardous voltage/current can cause
severe injury or death. Short circuits can cause bodily injury
and/or equipment damage.
connections with tools or jewelry while making adjustments or
repairs. Remove all jewelry before servicing the equipment.
Accidental starting can
Before working on the
WARNING
Moving parts.
Electrically ground the
Do not contact electrical
Section 6 Generator Reconnection
43