Battery voltage (Bt). This setting toggles between 12
and 24 VDC for the engine starting battery voltage. The
15/30RYG uses a 12-volt battery, Bt12.
Parameter
Unit's system voltage and
frequency, 15RYG
Unit's system voltage and
frequency, 30RYG
Unit configuration
Engine type
Engine data input types
Battery voltage
Communications
* ADC application program version 1.20 or higher
[ ADC application program version 1.21 or higher
Figure 5-1 Configuration Parameters
36
Section 5 Controller
Voltage, VAC
Setting
Uu01
120/240
Uu04
277/480
Uu10 *
120/240
Uu10 *
139/240
Uu11 *
120/208
Uu16 *
127/220
Uu01
120/240
Uu03
230/400
Uu04
277/480
Uu07 *
110/220
Uu10 *
120/240
Uu10 *
139/240
Uu11 *
120/208
Uu16 *
127/220
Uu17 *
110/190
Uu17 *
110/220
Uu18 *
120/208
Uu21 *
220/380
Uu22 *
240/416
Uu23 *
115/200
Uc01
Standby
Ec03
15RYG
Ec06
30RYG
Ed01
15/30RYG factory setup
Bt12
12 VDC
Cn00
No CAN communications
Cn01
J1939 (use for Remote Digital Gauge)
[
Cn06
Enables J1939 communications and 1-hour ADC power down after engine stop
for either:
a. Remote start/stop switch
b. Automatic transfer switch
c. Remote Digital Gauge with remote start/stop switch and replacement harness
Communications setting (Cn). This setting allows the
user to set the controller for communication with
optional meters. The 15/30RYG is factory-set for no
CAN communications, Cn00. Change this setting if the
optional Remote Digital Gauge is used.
Description
Frequency, Hz
Phases, Wires
Single phase, 3 Wire
60
Three phase, 4 Wire
60
Three phase, 4 Wire
60
60
Three phase, 4 Wire
60
Three phase, 4 Wire
Three phase, 4 Wire
60
Single phase, 3 Wire,
60
Three phase, 4 Wire
50
Three phase, 4 Wire
60
50
Single phase, 3 Wire
60
Three phase, 4 Wire
Three phase, 4 Wire
60
Three phase, 4 Wire
60
Three phase, 4 Wire
60
Three phase, 4 Wire
50
50
Three phase, 4 Wire
50
Three phase, 4 Wire
Three phase, 4 Wire
50
Three phase, 4 Wire
50
Three phase, 4 Wire
50
Connection
1 PH
Wye
Delta
Wye
Wye
Wye
1 PH
Wye
Wye
1 PH
Delta
Wye
Wye
Wye
Wye
Delta
Wye
Wye
Wye
Wye