Output Voltage Adjustment Mode:
Move the generator set master switch to the RUN position. The generator set
engine starts and the controller display shows the engine runtime hours.
Hold:
Wait about 5 seconds until the display changes from runtime hours
to the program version number.
Press the down arrow key and then the up arrow key 3 times to enter the
adjustment mode. (This is the controller "password.")
The controller is now in the voltage coarse adjustment mode.
Press:
or
or
Continued on Figure 5-7.
* Shaded boxes show which character in the controller display changes for each adjustment. X in the
examples above denotes any number from 0 to 9. The actual values may vary from model-to-model.
Figure 5-6 Output Voltage Adjustments
40
Section 5 Controller
To raise or lower the voltage in large increments
(approximately 5--7 volts per step).
To enter fine voltage adjustment mode.
To raise or lower the voltage in smaller increments
(approximately 0.5--0.7 volts per step).
Display :*
x x x x
x .
x x
x x
1 P
x x
1 P
x
x
1 P
TP6196