4.3 Remote Digital Gauge
The digital gauge allows for remote starting/stopping
and monitoring of certain generator set functions. See
Figure 4-4. (The remote digital gauge does not display
oil pressure for model 15/30RYG generator sets.) The
generator set has a
connector for connection to the remote digital gauge.
Refer to TT-1379 for instructions to install, connect, and
operate the remote digital gauge.
The ADC 2100 communications parameter Cn must be
set to Cn01 to communicate with the gauge.
Section 5.3.
If the ADC 2100 is configured for a CAN gauge
(communications parameter setting Cn01 or Cn02), the
controller remains powered continuously to maintain
communication with the gauge. If the ADC 2100 is not
configured
for
a CAN
parameter setting Cn00), the controller will power down
after 48 hours of no activity.
ADC 2100 application program version 1.14 or higher is
required for the remote digital gauge. Refer to TT-1285,
Program Loader Instructions, for instructions to load the
latest version of the controller application code, if
necessary.
3
1. SELECT button
2. UP arrow button
3. DOWN arrow button
Figure 4-4 Remote Digital Gauge
34
Section 4 Accessories
12-pin customer-interface
See
gauge (communications
1
2
Use one or more remote extension harness kits to
connect the gauge to the generator set. Do not use
more than 3 remote harness kits and do not exceed
22.86 m (75 ft.) in harness length. See Figure 4-5 for kit
selection.
Remote Extension
Harness Kit Number
GM32333-KP1
GM32333-KP2
Figure 4-5 Remote Extension Harness Kits
(For Gauge to Generator Set)
4.4 Block Heaters
Block heaters are available as installed accessories on
all generator sets. Use block heaters on all standby
applications where the generator set is subject to
temperatures below 16 C (60 F). Connect the block
heater to a power source that is energized when the
generator set is not running.
Note: Block heater damage. The block heater will fail
if the energized heater element is not immersed
in coolant. Fill the cooling system before turning
on the block heater. Run the engine until it is
warm and refill the radiator to purge the air from
the system before energizing the block heater.
Length
m (ft.)
4.6 (15)
7.6 (25)