Powering Up the Switch
Step 1
Verify that sufficient PSUs and fan modules are installed.
Step 2
Plug the power cables into the power supplies and arrange the cables so that they cannot be accidentally pulled out.
Depending on the outlet socket on your power distribution unit, you may need the optional jumper power
Note
cord to connect the switch to the outlet socket.
Step 3
Connect the other end of the power cables to the site power outlets that have the required power specification.
Step 4
Ensure that the switch is adequately grounded, as described in the
Step 5
Connect a terminal device to the serial console port. For more information, see the
Step 6
If using Power On Automatic Provisioning (POAP), insert the USB stick with the required files into the USB port.
Step 7
Turn the site power outlet switches to On. The switch boots automatically.
Step 8
Listen for the fans; they should begin operating as soon as the switch is powered on.
Note
Do not operate the switch without a functioning fan module, except briefly during the fan module replacement
procedure. Cisco MDS 9000 Series Switches can operate for only a few minutes without any functioning fan
modules before they begin to overheat.
Step 9
Verify that the LED behavior is as follows when the switch has finished booting:
• Fan status LED is green.
• Both LEDs on each PSU are green.
• The switch status LED is green. If this LED is orange or red, it indicates that one or more environmental monitors
is reporting a problem.
• The Ethernet port link LEDs should not be On unless the cable is connected.
Note
Step 10
If a component is not operating properly, try removing and reinstalling it. If it still does not operate correctly, contact
your customer service representative for a replacement.
If you purchased Cisco support through a Cisco reseller, contact the reseller directly. If you purchased support
Note
directly from Cisco, contact
Step 11
Verify that the system software has booted and the switch has initialized without error messages. If any problems occur,
see the
Cisco MDS 9000 Series System Messages
representative.
Step 12
If not using POAP, manually complete the initial configuration of the switch via the automatically launched setup script
through the console connection.
Step 13
Complete the worksheets provided in Site Planning and Maintenance Records for future reference.
A setup utility is automatically launched the first time you boot the switch and guides you through the basic
Note
configuration. For instructions about how to configure the switch and check module connectivity, see the
Cisco Fabric Manager Fundamentals Configuration
Cisco MDS 9148V-K9 Switch Hardware Installation Guide
44
The LEDs for the Fibre Channel ports remain orange until the ports are enabled, and the LED for the
management port remains Off until the port is connected.
Cisco Technical
Grounding the Switch
Support.
Guide. If you cannot resolve an issue, contact your customer service
Guide.
Connecting the Cisco MDS 9148V-K9 Switch
section.
Connecting the Console Port
section.