Download Print this page

Danfoss VLT DriveMotor FCP 106 Installation Manual page 7

Hide thumbs Also See for VLT DriveMotor FCP 106:

Advertisement

Available languages
  • EN

Available languages

  • ENGLISH, page 1
VLT® DriveMotor FCP 106
Installation Guide
ELECTRICAL SHOCK HAZARD - LEAKAGE CURRENT HAZARD
Leakage currents exceed 3.5 mA. Failure to connect the drive properly to protective earth (PE) can result in death or serious in-
jury.
-
Ensure reinforced protective earthing conductor according to IEC 60364-5-54 cl. 543.7 or according to local safety regula-
tions for high touch current equipment. The reinforced protective earthing of the drive can be done with:
-
a PE conductor with a cross-section of at least 10 mm
-
an extra PE conductor of the same cross-sectional area as the original PE conductor as specified by IEC 60364-5-54 with a
minimum cross-sectional area of 2.5 mm
ted).
-
a PE conductor completely enclosed with an enclosure or otherwise protected throughout its length against mechanical
damage.
-
a PE conductor part of a multi-conductor power cable with a minimum PE conductor cross-section of 2.5 mm
(permanently connected or pluggable by an industrial connector. The multi-conductor power cable shall be installed with an
appropriate strain relief).
-
NOTE: In IEC/EN 60364-5-54 cl. 543.7 and some application standards (for example IEC/EN 60204-1), the limit for requiring
reinforced protective earthing conductor is 10 mA leakage current.
THERMISTOR INSULATION
Risk of personal injury or equipment damage.
-
To meet PELV insulation requirements, use only thermistors with reinforced or double insulation.
EXCESSIVE HEAT AND PROPERTY DAMAGE
Overcurrent can generate excessive heat within the drive. Failure to provide overcurrent protection can result in risk of fire and
property damage.
-
Additional protective devices such as short circuit protection or motor thermal protection between drive and motor is re-
quired for applications with multiple motors.
-
Input fusing is required to provide short circuit and overcurrent protection. If fuses are not factory-supplied, the installer
must provide them.
PROPERTY DAMAGE
Protection against motor overload is not included in the default setting. The ETR function provides class 20 motor overload pro-
tection. Failure to set the ETR function means that motor overload protection is not provided and property damage can occur if
the motor overheats.
-
Enable the ETR function. See the programming guide for more information.
1.6 Safe Operation
When operating the unit, use the operating guide and programming guide for guidance and safety instructions.
The drive is not suitable as the only safety device in the system. Make sure that additional monitoring and protection devices on
drives, motors, and accessories are installed according to the regional safety guidelines and accident prevention regulations.
Keep all doors, covers, and terminal boxes closed and securely fastened during operation.
1.7 Verifying the Shipment and the Contents
Make sure that the items supplied and the information on the nameplate on the drive exterior match the order.
Danfoss A/S © 2022.09
W A R N I N G
2
(8 AWG) Cu or 16 mm
2
(14 AWG) (mechanically protected) or 4 mm
C A U T I O N
N O T I C E
N O T I C E
2
(6 AWG) Al.
2
(12 AWG) (not mechanically protec-
AN40855215838601-000101 / 130R1249 | 7
Instructions
2
(14 AWG)

Advertisement

loading