Drain pump delay
operation
Outline of specifications
1) When cooling operation mode (AUTO COOL, COOL, DRY) stopped, the following
three self-clean operations are performed.
Compressor
Self-clean
ON period
operation period
0 to 10 min.
None
10 to 60 min.
1 hour
60 min. to
2 hours
2) During operation of self-clean,
remote controller screen. However the operation lamp
(Green LED) goes off.
3) To stop the self-clean operation, push twice the
[ON/OFF] button on the remote controller continuously.
(Stop the operation as compressor ON time in the table
above: 10 minutes or below.)
4) When the follower unit executes self-clean operation in the
group connection, the segment of
wired remote controller screen via master unit.
∗ If self-clean operation is not used, set invalidity
(does not use) of the self-clean operation by changing
[0001 (At shipment) of CODE No. (DN) [D3] to [0000].
∗ To erase the
display during operation of self-clean,
change CODE No. [D4] from [0000: Display
(At shipment)] to [0001: Non-display].
(In the case of RBC-AMTU3∗)
SAVE
1) Turn on
button on the remote controller.
2) During operation of save operation,
wired remote controller.
3) During power save operation, the current release control
is performed with the restriction ratio set in EEPROM on
the outdoor unit.
4) The restriction ratio can be set by keeping
pushed for 4 seconds or more on the remote controller.
5) When validating the power save operation, the next
operation starts with power save operation valid because
contents are held even when operation stops, operation
mode changes or power supply is reset.
6) The restriction ratio can be set by changing the setup
data of CODE No. (DN) [C2] in the range of 50 to 100%
(every 1%, Setting at shipment: 75%).
* For RBC-AMSU5∗ remote controller, refer to its
owner's manual.
When a cooling operation (including dry operation) is
stopped, the drain pump continues operating for 5 minutes
to reduce drain water in drain pan.
FAN
Drain pump
Fan only
STOP
(UL)
lights on the wired
is displayed on the
SAVE
lights on the
SAVE
- 37 -
Remarks
Louver
Horizontal discharge position
It is recognized as
[STOP] from the
remote monitor side.
Carry out setting
operation during stop of
the unit; otherwise the
unit stops operation.
For the setup operation,
refer to "Power saving
mode" of Installation
Manual.