i-Controller 2.0 BACnet Communication Settings
Title
Overview
For proper data transfer to occur between the Building Management System (BMS) and the Flō i-Controller 2.0, the BACnet
communication connection must be properly configured. If the two controllers are not communicating and if the BMS
Communication Status displays 'Offline' in the BMS Status screen of the i-Controller, verify the following information.
CAUTION: Before connection, ensure there is no earth ground on the wires used for the RS485 connection.
Do not ground any of the wires connected to the RS485 terminal blocks inside the unit. Doing so will result in damage to
the i-Controller hardware.
i-Controller 2.0 BACnet Network Configuration
Verify the i-Controller protocol, address, and baud rate.
i-Controller 2.0 Settings
BMS Protocol: BACNET
Address: xx
Baud rate: 38400
BMS COMM STAT:
The "BMS Status" screen displays the current Flō i-Controller BMS protocol, BACnet address, baud rate and the status of
the connection to the BMS. If the Flō i-Controller is connected, the BMS status will display "Online". The BMS status will
display "Offline" if the BMS is offline or the Flō i-Controller is not connected or properly configured.
To change the communications protocol, address, perform the following steps:
1. From the Home Screen, press the program
2. Use the down arrow
BMS Configuration Screen.
3.
On BMS Connectivity page 1, you can set the controller address and baud rate.
4. Use the enter
5. Using the
and
6. Once the desired value has been reached press the
7. On BMS Connectivity page 2, you can set the communication protocol.
8. With the cursor back in the home position, at top right of screen, Use the down arrow
page2.
9.
Use the enter
EXTERNAL
Online
button to highlight "Communications" and press enter
button to navigate to the address field.
buttons increase and decrease the value as desired.
button to navigate to the value that you wish to change.
Figure 1. i-Controller BMS Status screen
button three times to navigate to the settings menu.
button to set the value.
enter
1
CN-IC2-15
button twice to navigate to the
button to navigate to
1-22AUG2022

Advertisement

loading

Summary of Contents for Flo CN-IC2-15

  • Page 1 Technical Guide CN-IC2-15 i-Controller 2.0 BACnet Communication Settings Title Overview For proper data transfer to occur between the Building Management System (BMS) and the Flō i-Controller 2.0, the BACnet communication connection must be properly configured. If the two controllers are not communicating and if the BMS Communication Status displays ‘Offline’...
  • Page 2 Technical Guide CN-IC2-15 i-Controller 2.0 BACnet Communication Settings Title 10. Using the buttons increase and decrease the value as desired. 11. Once the desired value has been reached press the button to set the value. enter 12. Once all changes have been completed, press, and hold the escape button to return to the Home Screen.
  • Page 3 Technical Guide CN-IC2-15 i-Controller 2.0 BACnet Communication Settings Title i-Controller 2.0 BACnet Network Connection to VCCX For Multiple Flō Units The Flō i-Controller 2.0 and AAON VCCX will come preconfigured with default addressing for the MAC address and Device ID set from the factory. The i-Controller 2.0 default MAC address and Device ID are set to the same number. Ex. Unit-1 will be MAC address = 1, Device ID = 1 and addressed consecutively for additional units.
  • Page 4 Technical Guide CN-IC2-15 i-Controller 2.0 BACnet Communication Settings Title i-Controller to VCCX addressing For Multiple Flō Units Navigate to the “Settings Menu” on the i-Controller 2.0 controller and verify the Device ID set for the VCCX controller. Refer to Table 2 for VCCX addressing information.
  • Page 5 Technical Guide CN-IC2-15 i-Controller 2.0 BACnet Communication Settings Title VCCX addressing For Multiple Flō Units Navigate to the “Settings” screen on the VCCX to verify / change MAC address and Device ID. Refer to Table 2 for VCCX addressing information.
  • Page 6 Technical Guide CN-IC2-15 i-Controller 2.0 BACnet Communication Settings Title 4. Use the “Up / Down” arrows to adjust Device ID. Press “Enter” button to move the cursor to the next field. When last field is edited, press “Enter” to save Device ID and the cursor will disappear. Press the “Enter”...