Rectifier Addressing

Each rectifier in the system has a unique address which identifies it to the monitor. This address is set by
the position in the rectifier shelf and the number of the shelf. It is read by the rectifier from the backplane
PCB and will change if the rectifier is moved to a new location. This address structure is set up when the
system is built by the system manufacturer.
2.6

Commissioning the Rectifier

1) Ensure the polarity of the load and battery cables to the backplane is correct.
2) Plug the rectifier into the rectifier shelf using the following steps:
Locate the metal tag (at the bottom/rear of the rectifier) into the chosen slot in the backplane.
Engage the plastic front panel into the slot at the front of the rectifier shelf.
Push the rectifier into the rectifier shelf until the connector is fully engaged.
Lock the rectifier in position using the plastic retainers in the front panel.
3) Once the rectifier is installed into the rectifier shelf, the AC power can be turned on. After the initial
start up period the rectifier will be set to the desired system parameters by the monitor module via
the serial communications.