ANY ANOMALIES AND REMEDIES

ANOMALY
The boiler gets dirty easily
The boiler does not reach the correct temperature
The boiler switches to thermal safety lock-out
The boiler is at the correct temperature but the
heating system is cold
Unburned material odour
Gas smell
Frequent safety valve triggering

ENVIRONMENTAL PROTECTION AND DISPOSAL

Protection and respect for the environment is a fundamental principle for ICI CALDAIE S.p.A. .
The quality of products, lower costs and protection of the environment are of equal importance for the company. ICI CALDAIE
S.p.A.
, also through ISO 14001 certification, strictly adheres to European laws and standards for the protection and preservation
of the environment.
In order to reduce its impact on the environment, the company uses the best technology and materials in its production processes
and always considers their economic impact.
Thermal insulators are special waste and must therefore be disposed of in compliance with the applicable legislation.
Maintenance
Cooke Industries - Phone: +64 9 579 2185 Email: sales@cookeindustries.co.nz Web: www.cookeindustries.co.nz
CAUSE
Badly adjusted burner
Clogged chimney
Dirt burner air path
Dirt boiler body
Wrong boiler/burner match
Insufficient power to the burner
Wrong adjustment
Wrong adjustment
Lack of water
Air presence
Presence of air in the system
Faulty circulation pump
Minimum Thermostat wrong adjustment (if any)
Faulty minimum Thermostat (if any)
Flue gases dispersion into the environment
Gas supply circuit
Excessive pressure in the system circuit
Malfunction of the system expansion vessel
REMEDY
Check the burner adjustment (flue gas analysis)
Clean the flue gas path and the chimney
Clean burner air coil
Clean the flue gas path
Compare burner data with tabulated matches
Check the burner adjustment
Check the correct operation
Check the set temperature
Check the correct operation
Check the set temperature
Check the electrical wiring
Check the probe bulbs
Check the circuit pressure
Check the circuit pressure
Check the vent valve
Vent the system
Unlock the circulation pump
Check the set temperature
Check the efficiency
Check the boiler body cleanliness
Check the flue gas pipe cleanliness
Check the tightness of boiler, flue gas pipe and
chimney
Check the door tightness
Check sealing, possible obstructions, combustion
quality
Check load pressure
Check pressure regulator
Check calibration
Check the efficiency
27