Installation Instructions: 252LRJS- -IEC
Deadbreak Elbow Connectors with Jacket Seal
CONTENTS:
Elbow Connector Housing, Compression Lug, Probe, Probe Wrench, Lubricant, Hold- -down Bail,
Installation Instructions.
The 252LRJS is designed to terminate UD jacketed and non--jacketed cable having concentric neutral wires or copper tape
shielding. The elbow provides a voltage test point and an operating interface for connecting to an 12/20 (24)kV 250ampere
deadbreak bushing or accessory device. Designed with a fold down extension on the cable entrance for sealing to the jacket of
jacketed cable. When other types of UD cable are to be terminated, an appropriate Elastimold cable shield or grounding device
must be used.
All apparatus must be de- -energized during installation
or removal of part(s).
Do not touch or move energized products in the work
area.
These instructions do not attempt to provide for every
possible contingency.
Failure to follow these instructions will result in
damage to the product and serious or fatal injury.
This product should be installed only by competent
personnel trained in good safety practices involving
high voltage electrical equipment. These instructions
are not intended as a substitute for adequate training or
experience in such safety practices.
FOR MORE INFORMATION ON PARTS, INSTALLATION RATINGS AND COMPATIBILITY, CALL THE NEAREST ELASTIMOLD OFFICE.
Limited Warranty:
1.
T&B warrants that its products will be free from defects in materials or workmanship for a period of two (2) years, except for tools which are warranted
separately (see warranty accompanying those products). Fisher Pierce products and Elastimold Reclosers are warranted for three years; and Joslyn
VBT and VBU capacitor switches are warranted for four years or 40,000 operations whichever occurs first. Upon prompt notification of a warranted defect,
T&B will, at its option, repair or replace the defective product.
2.
In no event shall T&B be liable for any consequential, indirect or special damages, nor will T&B be liable for transportation, labor, or other charges arising
out of the removal or reinstallation of its products. Liability for breach of warranty is limited to the cost of repair or replacement of the warranted product
only.
3.
Misuse, misapplication or modification of T&B products immediately voids all warranties.
THE WARRANTIES AND REMEDIES CONTAINED HEREIN ARE EXCLUSIVE AND ARE IN LIEU OF ALL OTHER WARRANTIES AND REMEDIES, INCLUDING
BUT NOT LIMITED TO ANY IMPLIED WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE, WHICH ARE SPECIFICALLY
DISCLAIMED.
IMPORTANT
1. Read entire installation instruction before starting.
2. Check contents of package to ensure they are complete
and undamaged.
3 Check elbow housing cable entrance size and
compression lug size to ensure proper fit with cable.
4. Check threads by threading probe into compression lug.
If resistance is encountered prior to full assembly, check
for damage and replace damaged component.
5. Unit Must be Bailed.
6. Have all required tools at hand and maintain cleanliness
throughout the procedure.
Caution:
If test point cap is not installed, lubricate cap and test point and install cap.
IS- - 1627
IS- - 252LRJS- - IEC
Date: December 2017
Printed in U.S.A.
DANGER
All apparatus must be installed and operated in
accordance with individual user, local and national
work rules and electrical standards.
For loadbreak products follow operating instructions.
All deadbreak connectors must be de- -energized before
operating. All 250A deadbreak connectors must be
mechanically secured with bails when connected.
If this product is supplied with a protective shipping
cover(s), remove this shipping cover(s) and replace
with
connector(s) before submerging or energizing the
circuit.
Inspect parts for damage, rating and compatibility with
mating parts.
Excess distortion of the assembled product may result
in its failure.
8155 T&B Boulevard, Memphis, Tennessee 38125
(800) 888- -0211 Fax: (800) 888- -0690
the
appropriate
HV
Probe
Compression Lug
Elbow Housing
ASSEMBLED ELBOW
IS- - 1627
IS- - 252LRJS- - IEC
Revision: 0
Page 1 of 5
insulated
cap(s)
or
Operating
Eye
Test Point
Intergral Cable
Jacket Seal